IMM AGS-2
47
Electrical Data Notes
1.
The field wire size designation is explained in
the table to the right that defines the number of
wires and conduit recommended. A “2” in
parenthesis (2) indicates that two conduits are
required.
2.
Allowable voltage limits
Unit nameplate 208V/60Hz/3PH: 187V to 229V
Unit nameplate 230V/60Hz/3Ph: 207V to 253V
Unit nameplate 380V/60Hz/3Ph: 342V to 418V
Unit nameplate 460V/60Hz/3Ph: 414V to 506V
Unit nameplate 575V/60Hz/3Ph: 517V to 633V
Maximum of 2 percent voltage unbalance.
3.
Unit wire size ampacity (MCA) is equal to 125% of the largest compressor-motor RLA plus 100%
of RLA of all other loads in the circuit including control transformer. Wire size ampacity for
separate 115V control circuit power is 15 amps.
4.
Compressor RLA values are for wire sizing purposes only but do reflect normal operating current
draw at unit rated capacity.
5.
Single point power supply requires a single disconnect to supply electrical power to the unit. This
power must be fused.
6.
Multiple point power supply requires two independent power circuits.
7.
All field wiring to unit power block or optional nonfused disconnect switch must be copper.
8.
Field wire size values given in tables apply to 75°C rated wire per NEC.
9.
External disconnect switch(s) or HACR breakers must be field supplied.
Note
: On single point power units a non-fused disconnect switch in the cabinet is available as an
option.
10.
All wiring must be done in accordance with applicable local and national codes.
11.
Recommended time delay fuse size or HACR breakers is equal to 150% of the largest compressor
motor RLA plus 100% of remaining compressor RLAs and the sum of condenser fan FLAs.
12.
Maximum time delay fuse size or HACR breakers is equal to 225% of the largest compressor-
motor RLA plus 100% of remaining compressor RLAs and the sum of condenser fan FLAs.
Power Limitations:
1.
Voltage within
±
10 percent of nameplate rating.
2.
Voltage unbalance not to exceed 2% with a resultant current unbalance of 6 to 10 times the voltage
unbalance per NEMA MG-1, 1998 Standard.
BAS Interface
Optional Protocol Selectability BAS interfaces: the locations and interconnection requirements for the
various standard protocols are found in their respective installation manuals, obtainable from the local
McQuay sales office, www.mcquay.com, and also shipped with each unit.
Modbus IM 743
L
ON
W
ORKS
IM 735
BACnet IM 736
Remote Operator Interface Panel
The box containing the optional remote interface panel will have installation instructions, IOM MT II
Remote, in it. The manual is also available for downloading from www.mcquay.com.
Sample
No. of Wires
No. of Conduit
350 MCM
3
1
2-250 MCM
6
1
(2) 250 MCM
6
2
(2) 2-250 MCM
12
2