Page 27
Description :
If this option is enabled, the panel will
attempt to power up in its previous state
when power is restorede.(e.g.Armed). If
it was previously armed it will ignore the
sector inputs for a settling period of 90
seconds and then re-arm. Any sectors
unsealed after this settling period will be
automatically isolated.
If this option is disabled then the panel will
power up in the OFF mode regardless of
its previous state.
Options :
0 = Do not retain status.
1 = Retain status.
NOTE: Pressing the OFF key during the 90 sec settling period will abort the rearm and
panel will stay in the OFF mode.
Example : While in program mode (Program LED flashing)
Key
Sequence
Operation
98
- Enter
Function
No.
1
-
Enter Option (1 = Retain status)
On
- Store
Entry
Installer may now exit program mode by pressing the OFF button or continue programming
by entering a new function number.
Description :
The Technician code is used to set up all
functions of the system. Tech code can
only be used when the system is in the
OFF mode.
Options : (6 digit entry required)
Any 6 Digits
Function 99 - Technician Code
Default - 218067 ( six digits )
Function 98 - Status on power up
Default - Do not retain status
Example : While in program mode (Program LED flashing)
Key
Sequence
Operation
99
- Enter
Function
No.
218067
-
Enter Option (Tech code = 218067)
On
- Store
Entry
Installer may now exit program mode by pressing the OFF button or continue programming
by entering a new function number.