Page 24
Function 89 - Single Digit Arming
Default - disabled
Options : (Single digit entry required)
0 = Single digit arming is disabled
1 = Single digit arming is enabled
Notes :
1.
When used for Smoke Detector Power (option 4), the Bell Output is used as the
negative supply to the Detectors. The Smoke Detector power may be turned off for 5
seconds when the panel is not armed by entering a user code and then TEST 6.
2.
When option 1 is selected and the keyswitch (Function 93) has been enabled, the bell output
will give :- 1 beep on disarm, 2 beeps on arming and 5 beeps if arming was unsuccessful
Description :
This function, when enabled, will allow the
panel to be turned on by pressing the 0 key
and either the 'ON' key for full arming or
'PARTIAL' key for partial arming.
Description :
This function determines what events will
trigger the bell 1 output
Options : (Single digit entry required)
0 -
Normal Bell Output
1 -
Normal Bell Arm/Disarm Chirps
2 -
Panel Secure
3 -
24 Hour input in Alarm
4 -
Smoke Detector Power
Function 91 - Bell Output Type
Default - Normal Bell Output
NOTE: If opening / closing reporting is enabled, the unit will report a quick arm report code 408
in CONTACT ID format or user 15 with ADEMCO high speed format.
Example : While in program mode (Program LED flashing)
Key
Sequence
Operation
89
- Enter
Function
No.
1
-
Enter Option (1 = single digit arming enabled)
On
- Store
Entry
Installer may now exit program mode by pressing the OFF button or continue programming by enter-
ing a new function number.
Function 90 - Default System Parameters
Description :
This option is used to default all system
setup values and user numbers etc,
back to known values.
Options :
None...this can be done by shorting the DEFAULT link
on the motherboard
Example : While in program mode (Program LED flashing)
Key
Sequence
Operation
90
- Enter
Function
No.
On
-
Panel will default to Factory defaults
Installer will automatically be exited from program mode when this function is entered and will have
to re-enter program mode using the default Technician code (218067 and the On key)
Example : While in program mode (Program LED flashing)
Key
Sequence
Operation
91
- Enter
Function
No.
2
-
Enter Option (2 = panel secure o/p)
On
- Store
Entry
Installer may now exit program mode by pressing the OFF button or continue programming by en-
tering a new function number.