i-32V5H MIDI
Chiller and Inverter Air/Water heat pumps with axial fan
22
0
10
20
30
40
50
60
70
80
90
0
0,2
0,4
0,6
0,8
1
1,2
1,4
1,6
1,8
2
2,2
2,4
2,6
p [kP
a]
ṁ [m
3
/h]
i-32V5H Midi 0126
p
ToutDS=45°C
ToutDS=55°C
0
10
20
30
40
50
60
70
80
90
0
0,2
0,4
0,6
0,8
1
1,2
1,4
1,6
1,8
2
2,2
2,4
2,6
p [kP
a]
ṁ [m
3
/h]
i-32V5H Midi 0132
p
ToutDS=45°C
ToutDS=55°C
p [kPa]
useful prevalence
ṁ [m3
/h]
water flow rate
4.3
UNIT AND AUXILIARY ELECTRICAL DATA
Unit power supply
V/~/Hz
400/3PH+PE/50
On-board control circuit
V/~/Hz
12/1/50
Remote control circuit
V/~/Hz
12/1/50
Fan power supply
V/~/Hz
400/3PH+PE/50
NOTE: Electrical data is subject to change due to updating. It is therefore always necessary to refer to the technical characteristics label at
-
tached to the unit.
5. CORRECTIVE FACTORS
5.1 CORRECTION FACTORS FOR USE OF WATER-GLYCOLE MIXTURE
The correction factors for water flow rate and pressure drop must be applied to the values obtained without the use of glycol. The correction
factor for water flow rate shall be calculated to maintain the same temperature difference as would be obtained without the use of glycol. The
pressure drop correction factor is applied to the water flow rate value corrected by the water flow rate correction factor.
Percentage of glycol
Freezing point [°C]
yeld corrector factor
Absorbed power
correction factor
Water flow correc
-
tion factor
Pressure drop correc-
tion factor
10%
-3,2
0,985
1
1,02
1,08
20%
-7,8
0,98
0,99
1,05
1,12
30%
-14,1
0,97
0,98
1,10
1,22
40%
-22,3
0,965
0,97
1,14
1,25
50%
-33,8
0,955
0,965
1,2
1,33
5.2
SCALING CORRECTION FACTOR
The correction factors due to contamination of the internal gas/water exchanger are shown below.
m
²
°C/kW
power output correction factor
power input correction factor
0,44 x 10
-¹
1,00
1,00
0,88 x 10
-¹
0,99
1,00
1,76 x 10
-¹
0,98
1,00
5.3
CALIBRATIONS AND PROTECTIONS CONTROL
Descrption
Value
High pressure switch
42,8 bar
High pressure alarm
41,5 bar
Low pressure alarm (cooling/heating)
3,5 bar / 1,3 bar
Maximum number of restarts/hour after high/low pressure alarm (manual reset)
3
Protezione antigelo (versione standard/versione BT)
3°C / -10°C