background image

i-32V5H MIDI 

Chiller and Inverter Air/Water heat pumps with axial fan

5

1. DESCRIPTION OF UNIT AND TECHNICAL SPECIFICATIONS 

The heat pumps in this series were designed for residential and commercial applications. They are extremely versatile and are designed for 

heat pump operation with hot water production for space heating and sanitary use at a temperature of 60°C. The use of the brushless inverter 

compressor technology, combined with the electronic expansion valve, the circulator and the variable speed fan, optimise the consumption and 

operating efficiency of the cooling components.

1.1 

FRAMEWORK

Structure suitable for outdoor installation consisting of thick profiles made of hot galvanised sheet steel and painted with polyester powder, co-

lour RAL 7035 textured, resistant to atmospheric agents. The removable panels allow maintenance inside the refrigeration and hydraulic circuits.

1.2 

COMPRESSORS

Twin rotary hermetic inverter controlled DC compressors, specifically designed to operate with R32, equipped with thermal protection and 

mounted on rubber vibration dampers.

This component is installed in a compartment separate from the air flow to reduce noise and is equipped with a crankcase heater that prevents 

the dilution of the oil by the refrigerant, ensuring correct lubrication and reducing wear on moving parts.

The compressors can be inspected by removing the side and front panels of the unit, allowing maintenance even when the unit is running.

1.3 

AIR SIDE HEAT EXCHANGER

The air exchangers are made of copper tubes and aluminium fins.The pipes are mechanically expanded in the alluminium fins to increase the 

heat exchange factor.The geometry of these exchangers allows a low value of pressure losses on the air side and therefore the possibility of using 

fans with a low number of revolutions (with a consequent reduction in machine noise).

On request, the coils can have surface treatments to allow greater resistance to corrosion or be made entirely of copper with a brass structure.

1.4 

UTILITY SIDE HEAT EXCHANGER 

Brazed plate heat exchanger made of AISI 304 stainless steel, covered with black flexible closed-cell elastomeric foam; thickness 9 mm, thermal 

conductivity (λ)≤0.036 W/mK (at air +20°C). A flow switch installed on the water side ensures the presence of water flow and, together with the 

protection probe, prevents the formation of ice inside.

The exchanger can be equipped with an electric antifreeze heater (optional accessory KA1) 

1.5 

FAN

The fans are axial type with airfoil blades They are statically and dynamically balanced and supplied complete with protection grille and air inlet 

and outlet with double flared profile, specially shaped to increase efficiency and reduce noise. The electric motor used is driven in modulation 

with brushless EC motor, directly coupled, and equipped with integrated thermal protection. The motor has an IP 54 protection rating according 

to CEI EN 60529.

1.6 

COOLING CIRCUIT

The cooling circuit is made of copper piping, brazed and assembled in the factory in accordance with EN 13134.The components present are:

• 

Filter drier with 100% molecular sieve cartridge;

• 

Shut-off valve on the liquid line;

• 

Liquid flow and moisture indicator;

• 

Electronic expansive valve;

• 

Charge connections;

• 

High-pressure safety pressure switches;

• 

High and low pressure transducers;

• 

Reverse cycle valve;

• 

Receiver and liquid separator.

The suction line is thermally insulated with flexible, closed-cell elastomeric foam.

Each unit is pressure tested to check for leaks and is supplied complete with a refrigerant charge optimised for operation.

Содержание i-32V5H MIDI 0121

Страница 1: ...ical specifications provided in this manual It is besides forbidden the reproduction under any form of the texts of the figures contained in this manual This manual is a translation from the official...

Страница 2: ...er and Inverter Air Water heat pumps with axial fan 2 00 01 2021 EM AR First emission Rev Date Compiled Approved Note Code Serie BTE01040101001 00_i 32V5 Midi_EN Chiller and Inverter Air Water heat pu...

Страница 3: ...il of connections and location 12 3 1 3 Weights 12 3 1 4 Location of the centre of gravity and vibrations dampers 12 3 2 TECHNICAL SERVICE AREAS 13 3 3 HYDRAULIC CIRCUIT 15 3 3 1 System water specific...

Страница 4: ...BLE 27 9 PERFORMANCE TABLES 29 9 1 HEATING 29 9 2 COOLING 30 9 3 SANITARY 31 9 4 DATA FOR ENERGY CERTIFICATION OF BUILDINGS ACCORDING TO UNI TS 11300 4 FOR HEAT PUMPS 32 9 4 1 Model i 32V5H MIDI 0121...

Страница 5: ...s allows a low value of pressure losses on the air side and therefore the possibility of using fans with a low number of revolutions with a consequent reduction in machine noise On request the coils c...

Страница 6: ...CER AF 1 AXIAL FAN PSH 1 HIGH PRESSURE SWITCH RD DELIVERY LIVE HKA 1 HEAT EXCHANGER ANTIFREEZE RESISTOR RL LIQUID LINE TE SD 1 SUCTION TEMPERATURE PROBE RS SUCTION LINE TE DT 1 EXHAUST TEMPERATURE PRO...

Страница 7: ...perature probes compressor thermal protection fan thermal protection flow switch on the water side to protect the evaporator high pressure switch 1 9 HYDRAULIC CYRCUIT The units in the series are supp...

Страница 8: ...lver Line anti corrosion treatment x x Electronic expansion valve x x Electronic circulator x x Water side safety valve x x Flow switch indication of flow presence x x Y filter x x Domestic hot water...

Страница 9: ...at exchanger which is activated when the temperature of the water inside the ex changer falls below 4 C For BT units this value must be set according to the percentage of glycol in the system and the...

Страница 10: ...is particularly suitable during night operation Below are the decreases in capacity and sound power level when the fan silent mode function is active The reduction refers to the test condition 3 of th...

Страница 11: ...temperature detection replicating the functionality of the on board control 3 INSTALLATION All handling installation and maintenance operations must be carried out by QUALIFIED PERSONNEL only Before...

Страница 12: ...Shipping weight kg Weight in service kg 0121 250 240 0126 250 240 0128 265 255 0132 265 255 3 1 4 Location of the centre of gravity and vibrations dampers The position of the centre of gravity of eac...

Страница 13: ...ice potential sources of danger The installation site of the unit must be free from foliage dust etc which could block or cover the heat exchange coils Installation should be avoided in areas subject...

Страница 14: ...ions in locations with strong winds refer to the area classification according to the Beaufort scale If the value is 7 strong wind average wind speed 13 9 17 1 m s it is strictly necessary to keep the...

Страница 15: ...an 1 mm obligatory to maintain the validity of the guarantee Charging unit and discharge valve where necessary CAUTION When dimensioning the pipes make sure that the maximum system side leakage is not...

Страница 16: ...hardness 4 5 8 5 dH Temperature 65 C Oxygen content 0 1 ppm Max quantity glycol 40 Phosphates PO4 2ppm Manganese Mn 0 05 ppm Iron Fe 0 3 ppm Alkalinity HCO3 70 300 ppm Chlorine ions Cl 50 ppm Sulphat...

Страница 17: ...I HEAT PUMP WITH DESUPERHEATER 5 Hi T2 REMOTE CONTROLLER 2 VDIS3 DIVERTER VALVE 6 SAS SANITARY PROBE 3 CADDY WATER STORAGE WITH DOMESTIC HOT WA TER EXCHANGER 7 FANCOIL TERMINALS 4 PUFFROLLER TECHNICAL...

Страница 18: ...water content it must be ensured that the pipes connecting to the unit have sufficient capacity to com pensate for this difference The additional volume required is shown in the table Model i 32V5H M...

Страница 19: ...k on In any case it is advisable to use an external tap to fill the system B A If the unit must be completely drained first close the manual inlet and outlet shutters not supplied and then disconnect...

Страница 20: ...pe R32 R32 R32 R32 Refrigerant quantity 7 kg 4 3 4 3 5 1 5 1 Refrigerant quantity in ton of CO2 equivalent 7 ton 2 90 2 90 3 44 3 44 Design pressure high low mod heat pump bar 42 8 1 3 42 8 1 3 42 8 1...

Страница 21: ...EATER The performance with desuperheater is shown under conditions 1 of the technical data table for water outlet temperatures of 45 C and 55 C from the desuperheater Model i 32V5H Midi Tout DS 45 C T...

Страница 22: ...l The correction factor for water flow rate shall be calculated to maintain the same temperature difference as would be obtained without the use of glycol The pressure drop correction factor is applie...

Страница 23: ...a function of altitude are calculated for cooling under the conditions 1 and for heating under the conditions 3 in the above technical data tables and are given for altitudes of 500 1000 1500 and 2000...

Страница 24: ...orking points shown below Flow rate m l s Useful head p models 0121 0126 kPa Useful head p model 0128 0132 kPa 0 5 107 4 111 2 0 6 103 5 108 7 0 7 98 6 105 5 0 8 92 7 101 5 0 9 85 8 96 7 1 0 78 0 91 2...

Страница 25: ...rate l s Three way pressure drops models 0121 0126 kPa Three way pressure drops models 0128 0132 kPa 0 5 0 75 0 75 0 6 1 08 1 08 0 7 1 47 1 47 0 8 1 92 1 92 0 9 2 43 2 43 1 0 3 00 3 00 1 1 3 62 3 62 1...

Страница 26: ...metric method The sound pressure values are calculated from the sound power level using ISO 3744 2010 considering units operating in the open area 7 1 POWER AND SOUND PRESSURE STANDARD Model i 32V5H M...

Страница 27: ...t when the flow switch intervention low rate i ncreasing flow is reached 8 2 CHILLER WATER PRODUCTION SUMMER OPERATION The minimum allowed evaporator outlet temperature is 5 C for units with standard...

Страница 28: ...10 5 0 5 10 15 20 25 30 35 40 Tacqua C Taria C Envelope heating CHILLER MODE 10 5 0 5 10 15 20 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 55 Tacqua C Taria C Envelope cooling Cooling Cooling BT DOM...

Страница 29: ...1 8 00 3 01 15 25 5 3 74 6 82 25 0 4 34 5 76 24 6 4 95 4 97 24 1 5 52 4 37 24 4 6 11 3 99 24 0 6 78 3 54 23 5 7 56 3 11 20 24 8 3 24 7 65 24 3 3 79 6 41 23 9 4 38 5 46 23 4 4 99 4 69 23 6 5 50 4 29 23...

Страница 30: ...4 04 5 45 23 9 4 11 5 82 35 17 7 6 00 2 95 18 7 6 19 3 02 20 6 6 32 3 26 21 9 5 35 4 09 24 0 5 47 4 39 26 2 5 56 4 71 40 16 5 6 60 2 50 17 5 6 75 2 59 19 3 6 90 2 80 20 7 5 90 3 51 22 6 6 02 3 75 24...

Страница 31: ...21 20 18 9 4 28 4 42 18 4 4 75 3 87 18 1 5 29 3 42 25 18 8 3 85 4 88 18 4 4 30 4 28 18 0 4 80 3 75 30 20 4 3 85 5 30 19 9 4 29 4 64 19 3 4 80 4 02 35 21 6 3 82 5 65 21 1 4 31 4 90 0126 20 23 6 5 50 4...

Страница 32: ...the heat pump referred to nominal conditions DC COPPL COP della pompa di calore nelle condizioni di parzializzazione definite dalla norma UNI EN 14825 9 4 1 Model i 32V5H MIDI 0121 Operating limits C...

Страница 33: ...5 45 55 7 17 3 17 3 17 0 7 2 44 2 14 1 80 2 24 1 24 0 23 4 2 3 49 2 92 2 37 7 26 0 25 8 25 1 7 4 04 3 28 2 64 12 25 3 25 0 24 1 12 4 70 3 83 2 64 Performance data measured under partial load condition...

Страница 34: ...68 4 26 5 39 7 06 COPDC 2 42 2 62 3 82 4 41 5 27 Performances 35 C SCOP s Energy class 4 29 169 A 9 4 4 Model i 32V5H MIDI 0132 Operating limits COLD source OUTDOOR AIR Operating temperature cut off...

Страница 35: ...MIDI Chiller and Inverter Air Water heat pumps with axial fan 35 Operating conditions F A E B C D COPPL 2 29 2 57 3 94 5 03 6 96 COPDC 2 34 2 53 3 54 4 09 4 90 Performances 35 C SCOP s Energy class 4...

Страница 36: ...by water flow rate at full load 9 5 1 Model i 32V5H MIDI 0121 Outside air dry bulb temperature C Charge factor F EER Cooling capacity kW 35 100 3 00 17 7 30 75 4 03 12 9 25 50 4 89 8 8 20 25 5 14 9 5...

Страница 37: ...30 40 50 60 70 80 90 100 EER F C Charge factor F EER 20 C xC 0 95 20 6 15 0 94 15 6 09 0 87 10 5 63 0 71 5 4 60 0 46 2 2 98 0 29 1 1 88 9 5 4 Model i 32V5H MIDI 0132 Outside air dry bulb temperature...

Страница 38: ...ange and or suc on the work environments Advice for safe use Do not breath in fumes or aerosol Storage Close carefully and store in a cool dry and well ven lated area Keep in original containers Incom...

Страница 39: ...i 32V5H MIDI Chiller and Inverter Air Water heat pumps with axial fan 39...

Страница 40: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: