i-32V5H MIDI
Chiller and Inverter Air/Water heat pumps with axial fan
34
Useful heating capacity / COP at nominal conditions with defrosting contibution
Useful heating capacity [kW]
COP
DC
T
air
(cold
source)
T
water
(hot source)
T
air
(cold
source)
T
water
(hot source)
35
45
55
35
45
55
-7
21,7
21,2
20,9
-7
2,62
2,21
1,86
2
27,0
27,7
26,9
2
3,82
3,01
2,45
7
28,0
28,3
27,3
7
4,41
3,45
2,73
12
26,2
26,6
25,6
12
5,27
4,03
3,14
Performance data measured under partial load conditions according to UNI EN 14825
Operating conditions
F
A (E)
B
C
D
T
air
[°C]
-10
-7
2
7
12
PLR
[%]
100
88
54
35
15
Power DC
(Declared Capacity)
[kW]
19,3
21,7
13,2
11,9
13,7
COP
PL
2,41
2,68
4,26
5,39
7,06
COP
DC
2,42
2,62
3,82
4,41
5,27
Performances
35 °C
SCOP
ηs
Energy class
4,29
169%
A++
9.4.4
Model i-32V5H MIDI 0132
Operating limits
COLD source
OUTDOOR AIR
Operating temperature (cut-off)
min
-20°C
max
35°C
HOT source
WATER
Operating temperature (cut-off)
min
25°C
max
60°C
Useful heating capacity / COP at nominal conditions with defrosting contibution
Useful heating capacity [kW]
COP
DC
T
air
(could
source)
T
water
(hot source)
T
air
(could
source)
T
water
(hot source)
35
45
55
35
45
55
-7
21,4
22,1
21,7
-7
2,53
2,16
1,82
2
31,4
32,2
31,0
2
3,54
2,90
2,37
7
32,1
32,7
31,8
7
4,09
3,30
2,64
12
30,2
30,8
29,6
12
4,90
3,86
3,00
Performance data measured under partial load conditions according to UNI EN 14825
Operating conditions
F
A (E)
B
C
D
T
air
[°C]
-10
-7
2
7
12
PLR
[%]
100
88
54
35
15
Power DC
(Declared Capacity)
[kW]
18,8
21,3
13,0
11,6
13,5