i-32V5H MIDI
Chiller and Inverter Air/Water heat pumps with axial fan
23
Descrption
Value
hydronic circuit safety valve
6 bar
*Check that the antifreeze mixture concentration is suitable for the freezing temperature.
5.4
CORRECTION FACTORS DEPENDING ON ALTITUDE
The correction factors for performance as a function of altitude are calculated for cooling under the conditions (1) and for heating under the
conditions (3) in the above technical data tables and are given for altitudes of 500, 1000, 1500 and 2000 m.
Altitude [m]
500
1000
1500
2000
correction factor heat output
0,9964
0,9941
0,9888
0,9869
Correction factor power input in heating mode
0,9931
0,9841
0,9853
0,9755
Correction factor cooling capacity
0,9888
0,9762
0,9618
0,9466
Correction factor power input in cooling mode
1,0106
1,0235
1,0386
1,0560