i-32V5H MIDI
Chiller and Inverter Air/Water heat pumps with axial fan
37
9.5.3
Model i-32V5H MIDI 0128
Outside air dry bulb
temperature [°C]
Charge factor
F%
EER
Cooling capacity
[kW]
35
100%
3,01
24,1
30
75%
4,12
17,7
25
50%
5,38
11,3
20
25%
5,67
12,3
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
EER
F%
C
Charge factor F%
EER @20°C xC
0,95
20%
6,15
0,94
15%
6,09
0,87
10%
5,63
0,71
5%
4,60
0,46
2%
2,98
0,29
1%
1,88
9.5.4
Model i-32V5H MIDI 0132
Outside air dry bulb
temperature [°C]
Charge factor
F%
EER
Cooling capacity
[kW]
35
100%
3,02
26,0
30
75%
4,15
19,1
25
50%
5,35
12,3
20
25%
5,87
12,6
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
EER
F%
C
Charge factor F%
EER @20°C xC
0,95
20%
6,30
0,94
15%
6,23
0,87
10%
5,77
0,71
5%
4,71
0,46
2%
3,05
0,29
1%
1,92