TEMPERATURE CONTROLLER 5002U-P
REF NO: m55A/om/201
Issue NO: 03
Page 28 of 35
Filter Effects:
Input (PV)
Filtering for 2 second
Filtering for 10 second
Control Output Selection:
OUTPUT TYPE
RELAY CAN CONFIGUR AS
RELAY1
RELAY2
RELAY3
RELAY4
ON-OFF ACTION
USE FOR CONTROL ACTION
ALARM2
ALARM3
ALARM4
P Action
USE FORCONTROL
HEAT/COOL ACTION
ALARM2
ALARM3
ALRAM4
None
ALARM1
ALARM2
ALARM3
ALARM4
10. CALIBRATION PROCEDURE
Calibration is provided for ambient temperature, PV sensor, inputRetransmission
output1 and output2.
First select the calibration function as described below and then follow the procedure
depending on the parameter to be calibrated. The sequences of parameters that will
be available for calibration are listed below:
Ambient temperature adjustment
PV sensor input
Retransmission1 output (calibration for voltage or current)
Retransmission2 output (calibration for voltage or current)
10.1 Ambient temperature adjustment
This menu will come up only if; the input sensor selected is Thermocouple type.
PV display shows
Amb.A
(Ambient temperature adjusts). SV display shows ambient
temperature measured by the controller and by applying old calibration data.
DP of last digit will blink to indicate that the value can be changed. Use Inc/Shift key to
adjust it to desired value. Once the desired value set and press ENT key, the blinking
DP will go off to indicate that the value has been registered. The controller will
automatically save all the new calculations. Ambient temperature adjustment is over.
Press MENU key to calibrate other parameters or press Escape key to come out to
normal operation.