background image

 

 

TEMPERATURE CONTROLLER  5002U-P 

 

                                        REF NO: m55A/om/201 

 

 

   Issue NO: 03 

 

Page 20 of 35 
 

(LOCK) 

1:L3on  
0:L3oF  

LoCk 

(LOCK) 

Lock LEVEL-4 
Calibration 

L4on

/

L4oF

 

1:L4on  
0:L4oF  

L4 ON 

 

S

.Pwd 

(S.Pwd) 

Password 
Set password to 
lock selected level 

0 to 9999 
 

if lock is on user 
can set 
password for all 
level 

 
 

6.6  Calibration 

Pressing MENU key PV Display shows 

Mode

 (mode) message. SV display shows 

CAL

 

(Cal)  Use  Inc  key  to  move  to  other  menu  levels.  Press  MENU  key  again  to  scroll 
through the menu items of particular level. For more detail refer Calibration procedure. 
 
 

Calibra tion:

 

Parameter 
(PV display) 

Settin g  name  and  
description  
(SV displa y)  

Default 
va lue  

Sho ws 
only if  

Symbol 

Name 

PWD 

(Pwd) 

Password 

0 to 9999(Password 
Protection for Level-4) 

-  

LOCK-4 set On 
in Level-3 

amb 

(Amb) 

Ambient  

Ambient Adjustment  

-  

PV Sensor 
type is T/c. 

Tc

.l

.s 

(tc.L.S) 

Thermocouple and  
Linear Span      
Calibration 

Depending on PV 
sensor type selected 

-  

Pv sensor type 
is T/c or Linear 

Rtd

.z 

(rtd.Z) 

Calibration Zero 
FOR RTD Input 

 

-  

PV Sensor 
type is RTD 

Rtd

.S 

(rtd.S) 

Calibration Span 
FOR RTD Input 

 

-  

PV Sensor 
type is RTD 

Rt1

.z 

(rtr.Z) 

Retransmission1 Zero 
calibration 

 

-  

 

Rt1

.S 

(rtr.S) 

Retransmission1Span 
calibration 

 

-  

 

Rt2

.z 

(rtr.Z) 

Retransmission2 Zero 
calibration 

 

-  

 

Rt2

.S 

(rtr.S) 

Retransmission2 Span 
calibration 

 

-  

 

 

6.7  Factory Reset Parameters

 

Pressing  MENU  key  PV  Display  shows

  Mode

  (mode)  message.  SV  display  shows 

F.rST

 (F.rST) Use Inc key to move to other menu levels. Press  MENU key again to 

scroll through the menu items of particular level. 

 

 

Содержание 5002U-P

Страница 1: ...RA AT TU UR RE EC CO ON NT TR RO OL LL LE ER R 5 50 00 02 2U U P P Masibus Automation Instrumentation Pvt Ltd B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India 91 79 23287275 79...

Страница 2: ...el Cutout Dimensions 7 2 3 How to connect wires 8 3 HARDWARE SPECIFICATION DETAILS 9 3 1 Inputs 9 3 2 Display Keys 9 3 3 Output 9 3 4 Communication Details 10 3 5 Power Supply 10 3 6 Physical 10 3 7 E...

Страница 3: ...sensor calibration 29 10 3 Retransmission1 and Retransmission2 output calibration Voltage current output 29 11 COMMUNICATION DETAILS 30 11 1 Function codes use for Modbus 30 11 2 Exception responses f...

Страница 4: ...ned in this manual are the trademarks or registered trademarks of Masibus Automation and Instrumentation P Ltd herein after referred to as MASIBUS Adobe Acrobat and Postscript are either registered tr...

Страница 5: ...ct is provided with the following accessories according to the model and suffix codes see the table below Check that none of them are missing or damaged No Item name Part number Qty Remarks 1 Mounting...

Страница 6: ...erminals mechanical vibrations are minimal corrosive gas is minimal temperature can be maintained at about 25 C to 35 C and the fluctuation is minimal no direct radiant heat is present no magnetic dis...

Страница 7: ...TEMPERATURE CONTROLLER 5002U P REF NO m55A om 201 Issue NO 03 Page 7 of 35 2 2 External Dimensions and Panel Cutout Dimensions Unit mm...

Страница 8: ...e low conductor resistance and cause no significant differences in resistance between the three wires Do not connect Terminal 23 when thermocouple or Linear input is selected Use repeater after each s...

Страница 9: ...MRR 120 dB Temp co 100ppm C Input Impedance 1M Max Voltage 20VDC Protection Wire beak detection of any wire Resolution 0 1 degC For G C TC 1 0 C 1 Count 3 2 Display Keys Front Panel Details PV Display...

Страница 10: ...Between primary terminals and grounding terminal At least 1500 V AC for 1 minute Between grounding terminal and secondary terminals At least 1500 V AC for 1 minute Between secondary terminals At leas...

Страница 11: ...Humidity 20 95 RH non condensing Tempco FOR PV 100ppm FOR Retransmission Current and Voltage 150ppm Instrument Warm up Time 15 minutes after power on 3 8Special Feature Square RootExtraction Input Sca...

Страница 12: ...rt Function Process Value Display PV Display process value Display parameter name when user set parameter Display error message when an error occurs Set Value Display SV Display set value Display para...

Страница 13: ...in it rollovers to 0 SHIFT KEY DECREMENT KEY It is used to Shift the digit to set the parameter as describe in increment key when DP decimal point started to blink Menu key is used to go forward to sh...

Страница 14: ...ROLLER 5002U P REF NO m55A om 201 Issue NO 03 Page 14 of 35 Example How to change SET POINT SP 1 will be shown in operator mode and they can be editable NOTE ALL other parameters can EDIT according to...

Страница 15: ...lay Setting name and description SV Display Default value Shows only if Symbol Name PWD Pwd Password 0 to 9999 Password Protection for Level 1 LOCK 1 set on in Level 3 A1 SP A1 SP Alarm 1 Set point PV...

Страница 16: ...Y Alarm 3 Hysteresis 1 to 250 2 A3 LC A3 LC Alarm 3 Logic norm flsf 0 norm 1 FLSF Normal A3 Dy A3 Dy Alarm 3 Delay 1 to 99 seconds 10 A3 lt A1 LT Alarm 3Latch Yes no 1 YES 0 no 0 A4 SP A4 SP Alarm 4 S...

Страница 17: ...range high setting span zero Range of the sensor Table 6 1 1999 to 9999 for linear input types 1370 Pv Lo Pv Lo Process value range lower setting 200 In hi IN HI Input value range higher setting Inpu...

Страница 18: ...her menu levels Press set key again to scroll through the menu items of particular level LEVEL 3 Functional Parameters Configuration Part 2 Parameter PV display Setting name and description SV display...

Страница 19: ...Output Type 0 20 4 20 0 5v 1 5v 0 10v 0 0 20 0 20mA 1 4 20 4 20mA 2 0 5 0 5volt 3 1 5 1 5volt 4 0 10 0 10volt 4 20 mA r2 dr r dir Retransmission 2 direction Dir rev 1 dir 0 rev Dir Rt2 h rtr H Retran...

Страница 20: ...ws only if Symbol Name PWD Pwd Password 0 to 9999 Password Protection for Level 4 LOCK 4 set On in Level 3 amb Amb Ambient Ambient Adjustment PV Sensor type is T c Tc l s tc L S Thermocouple and Linea...

Страница 21: ...evel 3 Also PASSWORD can be set using S Pwd S PWD INPUT TYPE SELECTION TABLE Table 6 1 Type I P NO Type Display Range Accuracy Resolution E 1 E tc 200 to 1000 C 0 1 of instrument range 1 digit for tem...

Страница 22: ...TEMPERATURE CONTROLLER 5002U P REF NO m55A om 201 Issue NO 03 Page 22 of 35 7 PARAMETER FLOW CHART...

Страница 23: ...REF NO m55A om 201 Issue NO 03 Page 23 of 35 NOTE It is important that the controller be set up in proper manner Failure to do so could result in incorrect operation as changing some parameters will...

Страница 24: ...Ref figure 6 9 P A H C Absolute value High control Ref figure 1 10 P A H A Absolute value High alarm Ref figure 1 11 P A L C Absolute value Low control Ref figure 2 12 P A L A Absolute value Low alar...

Страница 25: ...ere are shown considering the setting is Normal If the settings are Fail Safe the relays will behave exactly the opposite way However it s worth mentioning that the relays will be in off de energized...

Страница 26: ...trol logic user has to program the proportional band for proper control They can be changed manually as explained in control parameters Control Parameter Proportional Band Proportional action is the a...

Страница 27: ...ser programmable value this allows the user to preprogram the approximate output requirement at the setpoint to allow for quicker settling atset point when Automatic reset Integral time set to zero Ra...

Страница 28: ...calibration are listed below Ambient temperature adjustment PV sensor input Retransmission1 output calibration for voltage or current Retransmission2 output calibration for voltage or current 10 1 Amb...

Страница 29: ...ions Depending on the situation this process may take few seconds to calibrate Once zero is calibrated press MENU key for RTD span calibration PV shows the message RTD S rtd S calibration Span SV disp...

Страница 30: ...6 Preset Single register Use to write programmable register 11 2 Exception responses for Modbus 11 3 Modbus parameters Sr No Parameter Absolute address Data Type Minimum value Maximum value Access Typ...

Страница 31: ...AL2 HYS 40010 Integer 1 250 R W 11 AL2 LC 40011 Char 0 1 R W 12 AL2 DLY 40012 Char 1 99 R W 13 AL2 LT 40013 Char 0 1 R W 14 AL3 SP 40014 Integer 1999 9999 R W 15 AL3 TP 40015 Char 0 22 R W 16 AL3 HYS...

Страница 32: ...40052 Char 0 4 R W 53 Retransmission 2 Direction 40053 Char 0 1 R W 54 Retransmission 2 Range high 40054 Integer 5 00 105 00 R W 55 Retransmission 2 Range low 40055 Integer 5 00 105 00 R W 56 Retransm...

Страница 33: ...parameters value refer in MENU LAYOUT 12 APPENDIX 12 1 Troubleshooting If the operating display does not appear after turning on the controller s power follow the measures in the procedure below If a...

Страница 34: ...n it may not show oPEn OPEN message instead it will show either oVER UnDR OVER UNDER 12 3 Retransmission Output Table for OPEN OVER UNDER Condition RETRASMISSI ON VARIABLE PROCES S SCALE RETRASMISSI O...

Страница 35: ...ED NORMAL ABNORMAL UP DOWN ACK IN ABNORMAL CONDITION NORMAL ACK IN NORMAL CONDITION HIGH ALARM LED LATCH YES LED OFF FLASH FLASH OFF STEADY STEADY OFF RELAY OFF ON ON OFF OFF OFF OFF ALARM LED LATCH N...

Отзывы: