TEMPERATURE CONTROLLER -5002U-P
REF NO: m55A/om/201
Issue NO: 03
Page
21
of
35
Factor y Res et Mode :
Parameter
(PV display)
Setting name a nd
descr iption
(SV d isp la y)
Def ault
va lue
Sho ws on ly
if
Symbol
Name
Pwd
(Pwd)
Pass word
0 to 9999
-
-
L
.def
(L.dEF)
LOAD Def ault
CAL
\
PARA
(CAL)\(PARA)
CAL- Only calibration
set to default value
PARA- All parameters
excluding calibration will
set to default value
-
Note: -
Factory reset will load default parameters, as mention in MENU LAYOUT
(Default value). Once this function applies, user has to switch off the instrument and
again switch on the instrument to work according to Default values.
Note: -
In menu layout, for each level PASSWORD will be enable using LOCK
ON/OFF selection in Level-3. Also, PASSWORD can be set using
S.Pwd
(S.PWD)
INPUT TYPE SELECTION TABLE:
Table 6.1
T yp e
I / P
N O
T yp e
D is p l a y
R a n g e
Ac c u r a c y
R e s o lu t io n
E
1
E tc
- 2 0 0 t o 1 0 0 0
C
+0.1% of instrument range
+ 1 digit for temperature
Equal to or higher than 0º c
+ 0.2% of instrument range
+ 1 digit for temperature
Below 0º c
+ 0 . 2 % o f i n s t r u m e n t
r a n g e + 1 d i g it ( B , R , S
t yp e T C )
0 . 1 ° C
J
2
J tc
- 2 0 0 t o 1 2 0 0
C
K
3
K tc
- 2 0 0 t o 1 3 7 0
C
T
4
T tc
- 2 0 0 t o 4 0 0
C
B
5
B tc
4 5 0 t o 1 8 0 0
C
R
6
R tc
0 t o 1 7 5 0 ° C
S
7
S tc
0 t o 1 7 5 0
C
N
8
n tc
- 2 0 0 t o 1 3 0 0 ° C
C
20
C tc
0 t o 2 3 1 0 ° C
+ 0 . 1 % o f i n s t r u m e n t
r a n g e + 1 d ig i t
1 ° C
G
21
G tc
0 t o 2 3 1 0 ° C
RTD
9
RTD
- 1 9 9 . 9
t o
8 5 0 . 0
C
+ 0 . 1 % o f i n s t r u m e n t
r a n g e + 1 d ig i t
0 . 1 ° C
-10 to 20mV
10 -10
.20
- 1 9 9 9 t o 9 9 9 9
C o u n t s
+ 0 . 1 % o f i n s t r u m e n t
r a n g e + 1 d ig i t
1 C o u n t
0 to 75mv
11
0-75
0 to 100mV
12 0-100
0 to 2V
13
0-2v
0.4 to 2V
14
0
.4-2
4 to 20mAmp
15
4-20
0 to 20mAmp
16
0-20
0 to 5V
17
0-5V
1 to 5V
18
1-5V
0 to 10V
19 0-10v