TEMPERATURE CONTROLLER 5002U-P
REF NO: m55A/om/201
Issue NO: 03
Page 18 of 35
Rdly
(
(rdly)
))
Relay Delay
0 to 99
0
SQrt
(Sqrt)
Square Root for
Linear Inputs Type
Yes
/
no
1:(YES)
0:(no)
No
Input type
selected is
linear
SP
.no()
(SP.no)
Set
point
selectiontodisplay
set point in RUN
mode
1
/
2
/
3
/
4
1:(sp.1)
2:(sp.2)
3:(sp.3)
4:(sp.4)
1 (Set
Point
–1)
fltr
(FLtr)
Filter for Process
value
(1
st
order low-pass
IIR filter)
0 to 60 seconds
5
6.5 LEVEL - 3
Pressing MENU key for 3 seconds (approx.) PV Display shows Mode (mode)
message. SV display shows
Lvl3
(LvL3) Use Inc key to move to other menu levels.
Press set key again to scroll through the menu items of particular level.
LEVEL 3: Functional Parameters Configuration Part-2
Parameter
(PV display)
Setting
n ame
and de scriptio n
(SV d isp la y)
Def ault
va lue
Sho ws on ly
if
Symbol
Name
PWD
(Pwd)
Password
0 to 9999(Password
Protection for Level-
3)
-
LOCK-3 set on
in Level-3
Sr
.no
(Sr.no)
Unit ID
1 to 247
1
-
BAUd
(bAUd)
Communication
Baud rate
9600
/
19.2K
0:(9600)
– 9600
bps
1:(19.2K)
–19.2
Kbps
19.2k bps
Pr
.St
.
(Pr.St)
Parity/Stop bit
selection
p
.n
.S
.1
/
P
.nS
.2
/
P
.o
.s1
/
P
.ES
.1
0:(P.N.S.1)-parity
none-stop bit-1
1:(P.N.S.2)-parity
none - stop bit-2
2:(P.O.S.1)-parity
odd -stop bit-1
3:(P.E.S.1)-parity
even - stop bit-1
No parity
/Stop bit
- 2
Rt1
.t
(rtr.t)
Retransmission 1
Output Type
0-20
/
4-20
/
0-5v
/
1-5v
0-10v
4-20 mA