TEMPERATURE CONTROLLER -5002U-P
REF NO: m55A/om/201
Issue NO: 03
Page
15
of
35
6. MENU LAYOUT
6.1 Run Time Indication/Function
Following parameters can view or change during run time.
For Thermocouple input type, Press Inc key to show ambient temperature.
6.2 Set Point Setting
Pressing MENU key PV Display shows
sp.1
(SP.1) message . SV display shows
Set
Point Value
Use Inc and shift key to modify value. OR press MENU key again to set
value for next parameter.
6.3 LEVEL
– 1
Pressing MENU key for 3 seconds (approx.) PV Display shows
Mode
(mode)
message. SV display shows
Lvl1
(LvL1) Use Inc key to move to other menu levels.
LEV EL 1: A larm Sett ing s
Parameter(P V d isp la y)
Setting name a nd
descr iption
SV Disp la y
Def ault
va lue
Sho ws on ly if
Symbol
Name
PWD
(Pwd)
Password
0 to
9999( Pass word
Protection f or
Le ve l-1)
-
LOCK-1 set on in
Level-3
A1
.SP
(A1.SP)
Alarm 1 Set point
PV range selected
1
0
Output Type is none
A1
.tP
(A1.tP)
Alarm 1 Type
0 to 22. Refer alarm
type Table-8.1
0 (none)
Output Type is none
A1
.HY
(A1.HY)
Alarm 1 Hysteresis
1 to 250
2
Output Type is none
A1
.lC
(A1.LC)
Alarm 1 Logic
(normal or fail safe
selection)
norm
/
flsf
0:(norm)
1: (FLSF)
Normal
Output Type is none
A1
.dY
(A1.Dy)
Alarm 1 Delay
1 to 99 seconds
10
Output Type is none
a1
.lt
(A1.LT)
Alarm 1 Latch
Yes
/
no
1:(YES)
0:(no)
0
Output Type is none
A2
.SP
Alarm 2 Set point
PV range selected
1
0
S e t Po i n t Se t t i n g :
Parameter
(PV display)
Setting name and description
(SV displa y)
Default
va lue
Symbol
Name
Sp
.1
(SP.1)
Target Set point-1 Depending on PV sensor type selected 200