HydroBank MS Installation and Operation Manual MAMM-WSHP-IOM-1MSA (October 2014)
37
Electrical Data
Figure 31: Electrical Data - Vertical Units, Constant Torque ECM Blower Motor
Electrical Data - Vertical Units, Constant Torque ECM Blower Motor
RLA
LRA
D
208/230-1-60
5.4
29
3.5
1/2
8.9
10.3
15
20
E
265/277-1-60
5.0
28
3.2
1/2
8.2
9.5
15
20
D
208/230-1-60
7.3
43
3.5
1/2
10.8
12.6
15
20
E
265/277-1-60
5.9
46
3.2
1/2
9.1
10.6
15
20
D
208/230-1-60
8.9
43
3.5
1/2
12.4
14.6
15
25
F
208/230-3-60
6.3
63
3.5
1/2
9.8
11.4
15
20
E
265/277-1-60
6.8
46
3.2
1/2
10.0
11.7
15
20
G
460-60-3
3.1
30
2.1
1/2
5.2
6.0
15
20
D
208/230-1-60
11.2
54
3.5
1/2
14.7
17.5
20
25
F
208/230-3-60
7.0
63
3.5
1/2
10.5
12.3
15
20
E
265/277-1-60
8.5
45
3.2
1/2
11.7
13.8
15
20
G
460-60-3
3.6
30
2.1
1/2
5.7
6.6
15
20
D
208/230-1-60
14.4
74
3.5
1/2
17.9
21.5
25
35
F
208/230-3-60
9.1
70
3.5
1/2
12.6
14.9
15
20
E
265/277-1-60
10.5
67
3.2
1/2
13.7
16.3
20
25
G
460-60-3
3.9
34
2.1
1/2
6.0
7.0
15
20
D
208/230-1-60
F
208/230-3-60
G
460-3-60
D
208/230-1-60
15.0
88
3.5
1/2
18.5
22.3
25
35
F
208/230-3-60
10.1
68
3.5
1/2
13.6
16.1
20
25
G
460/60/3
4.4
34
2.1
1/2
6.5
7.6
15
20
D
208/230-1-60
17.4
84
5.0
1
22.4
26.8
30
40
F
208/230-3-60
10.9
88
5.0
1
15.9
18.6
20
25
G
460/60/3
5.3
44
4.6
3/4
9.9
11.2
15
20
D
208/230-1-60
24.9
134
5.0
1
29.9
36.1
35
60
F
208/230-3-60
16.6
110
5.0
1
21.6
25.8
25
40
G
460/60/3
7.2
52
4.6
3/4
11.8
13.6
15
20
D
208/230-1-60
27.2
178
5.0
1
32.2
39.0
40
60
F
208/230-3-60
19.3
136
5.0
1
24.3
29.1
30
45
G
460/60/3
8.3
66
4.0
1
12.3
14.4
15
20
Consult Factory
*NEUTRAL CONNECTION REQUIRED! All 460 VAC units with constant-torque ECM motors require a four-wire power supply with
neutral. The motor is 265-277V/1Ph and is wired between one hot leg and neutral.
060
070
019
024
030
036
048
Blower
Motor HP
Total Unit
FLA
042
040
015
Voltage
Code
Rated Voltage
Compressor
Blower
Motor FLA
Unit
Size
Max. Fuse
Min Circuit
Amps
Min. Fuse