33
Operating Pressures and Temperatures
Table 14: Operating Pressures and Temperatures - Vertical Unit Sizes 048, 060, 070
Entering
Water Temp
°F
Water
Flow GPM
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
8.4
71-81
273-293
6-11
3-8
6-8
19-25
12.0
72-82
275-295
7-12
3-8
4-6
19-25
14.4
74-84
278-298
7-12
2-7
3-5
19-25
8.4
123-133
178-198
12-17
8-13
16-18
22-28
88-98
293-313
7-12
3-8
7-9
22-28
12.0
123-133
169-189
12-17
7-12
11-13
22-28
90-100
296-316
8-13
3-8
5-7
22-28
14.4
123-133
166-186
12-17
6-11
9-11
22-28
91-101
299-319
8-13
2-7
4-6
23-29
8.4
129-139
240-260
6-11
9-14
16-18
22-28
123-133
321-341
8-13
3-8
9-11
28-34
12.0
129-139
228-248
6-11
8-13
11-13
22-28
126-136
324-344
8-13
3-8
7-9
29-35
14.4
129-139
223-243
6-11
7-12
9-11
22-28
128-138
327-347
9-14
2-7
5-7
29-35
8.4
138-148
318-338
5-10
10-15
15-17
20-26
159-169
355-375
11-16
3-8
11-13
34-40
12.0
138-148
303-323
5-10
8-13
10-12
20-26
162-172
359-379
11-16
3-8
8-10
34-40
14.4
138-148
297-317
5-10
7-12
8-10
20-26
165-175
363-383
12-17
2-7
6-8
35-41
8.4
142-152
422-442
5-10
11-16
14-16
18-24
12.0
142-152
401-421
5-10
9-14
9-11
18-24
14.4
142-152
393-413
5-10
8-13
8-10
18-24
Entering
Water Temp
°F
Water
Flow GPM
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
10.5
67-77
282-302
7-12
1-6
6-8
19-25
15.0
69-79
285-305
8-13
1-6
4-6
19-25
18.0
70-80
288-308
8-13
1-6
3-5
20-26
10.5
118-128
179-199
14-19
9-14
16-18
22-28
83-93
304-324
8-13
1-6
7-9
22-28
15.0
118-128
170-190
14-19
7-12
11-13
22-28
85-95
307-327
9-14
1-6
5-7
23-29
18.0
118-128
167-187
14-19
7-12
9-11
22-28
87-97
310-330
10-15
1-6
4-6
23-29
10.5
124-134
242-262
8-13
10-15
15-17
21-27
117-127
332-352
9-14
1-6
9-11
29-35
15.0
124-134
230-250
8-13
8-13
11-13
21-27
120-130
336-356
10-15
1-6
7-9
29-35
18.0
124-134
225-245
8-13
8-13
9-11
21-27
122-132
339-359
10-15
1-6
5-7
30-36
10.5
132-142
321-341
6-11
11-16
14-16
20-26
151-161
368-388
12-17
1-6
11-13
34-40
15.0
132-142
305-325
6-11
9-14
10-12
20-26
154-164
371-391
13-18
1-6
8-10
35-41
18.0
132-142
299-319
6-11
8-13
8-10
20-26
157-167
375-395
14-19
1-6
6-8
36-42
10.5
136-146
425-445
6-11
12-17
14-16
18-24
15.0
136-146
404-424
6-11
10-15
9-11
18-24
18.0
136-146
396-416
6-11
9-14
8-10
18-24
Entering
Water Temp
°F
Water
Flow GPM
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
12.6
67-77
282-302
7-12
2-7
6-8
20-26
18.0
68-78
284-304
8-13
2-7
4-6
20-26
21.6
70-80
287-307
9-14
2-7
3-5
21-27
12.6
117-127
171-191
14-19
7-12
15-17
23-29
83-93
303-323
9-14
2-7
7-9
24-30
18.0
117-127
162-182
14-19
6-11
10-12
23-29
85-95
306-326
9-14
2-7
5-7
24-30
21.6
117-127
159-179
14-19
5-10
9-11
23-29
86-96
309-329
10-15
2-7
4-6
24-30
12.6
124-134
230-250
8-13
8-13
15-17
22-28
116-126
331-351
9-14
2-7
9-11
30-36
18.0
124-134
219-239
8-13
7-12
10-12
22-28
119-129
335-355
10-15
2-7
6-8
30-36
21.6
124-134
214-234
8-13
6-11
8-10
22-28
121-131
338-358
11-16
2-7
5-7
31-37
12.6
132-142
305-325
6-11
8-13
14-16
21-27
150-160
367-387
13-18
2-7
10-12
36-42
18.0
132-142
290-310
6-11
7-12
9-11
21-27
153-163
370-390
14-19
2-7
7-9
36-42
21.6
132-142
284-304
6-11
6-11
8-10
21-27
156-166
374-394
15-20
2-7
6-8
37-43
12.6
136-146
405-425
6-11
10-15
13-15
19-25
18.0
136-146
385-405
6-11
8-13
9-11
19-25
21.6
136-146
377-397
6-11
7-12
7-9
19-25
Vertical 060
Full Load Cooling
Full Load Heating
Vertical 048
Full Load Cooling
Full Load Heating
30
Out of Range
40
60
80
100
Out of Range
30
Out of Range
40
60
80
Out of Range
Vertical 070
Full Load Cooling
Full Load Heating
30
Out of Range
100
40
60
80
100
Out of Range