HydroBank MS Installation and Operation Manual MAMM-WSHP-IOM-1MSA (October 2014)
Unit Checkout Sheet
Unit Checkout Sheet
WSHP UNIT CHECK-OUT SHEET
Customer Data
Customer Name ____________________________ Date _____________________________________________
Address _____________________________________________________________________________________
Phone ____________________________________ Unit Number ________________________________________
Unit Nameplate Data
Make _________________ Model Number ________________ Serial Number ____________________________
Compressor:
RLA __________________ LRA ___________ Refrig, Charge (oz.) ________
Blower Motor(s):
FLA (or NPA) ___________ HP ___________
Maximum Fuse Size: (Amps) ________________ Minimum Circuit Ampacity (Amps) _____________
Operating Conditions
Unit Conditions
Cooling Mode
Heating Mode
Measured At:
Entering Air Temperature
_____________
_____________
_____________________________
Leaving Air Temperature
_____________
_____________
_____________________________
Entering Fluid Temperature
_____________
_____________
Leaving Fluid Temperature
_____________
_____________
Fluid Flow (gpm)
_____________
_____________
Fluid Side Pressure Drop
_____________
_____________
Compressor
Mode
Cooling
Suction Pressure (psig)
_______
Discharge Pressure (psig)
_______
Suction Temp (at compressor)
_______
Discharge Temp (at compressor)
_______
Suction Superheat (at compressor)
_______
Liquid Line Leaving Condenser Temp _______
Liquid Subcooling
_______
Volts/Amps
Phase
L1
L2
L3
Compressor Volts
_____ _____ _____
Compressor Amps
_____ _____ _____
Blower Volts
_____ _____ _____
Blower Amps
_____ _____ _____