32
HydroBank MS Installation and Operation Manual MAMM-WSHP-IOM-1MSA (October 2014)
Operating Pressures and Temperatures
Table 13: Operating Pressures and Temperatures - Vertical Unit Sizes 030, 036, 042
Entering
Water Temp
°F
Water
Flow GPM
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
4.9
69-79
274-294
5-10
4-9
6-8
18-24
7.0
71-81
277-297
6-11
4-9
5-7
18-24
8.4
72-82
280-300
6-11
4-9
4-6
19-25
4.9
120-130
177-197
11-16
7-12
16-18
21-27
86-96
295-315
6-11
4-9
8-10
21-27
7.0
120-130
168-188
11-16
6-11
11-13
21-27
88-98
298-318
7-12
4-9
6-8
21-27
8.4
120-130
164-184
11-16
5-10
9-11
21-27
90-100
301-321
7-12
4-9
5-7
22-28
4.9
127-137
238-258
6-11
9-14
16-18
20-26
121-131
323-343
7-12
4-9
10-12
27-33
7.0
127-137
226-246
6-11
7-12
11-13
20-26
124-134
326-346
7-12
4-9
7-9
27-33
8.4
127-137
222-242
6-11
6-11
9-11
20-26
126-136
329-349
8-13
4-9
6-8
28-34
4.9
135-145
316-336
4-9
9-14
15-17
19-25
156-166
357-377
9-14
4-9
12-14
32-38
7.0
135-145
300-320
4-9
7-12
10-12
19-25
159-169
361-381
10-15
4-9
8-10
33-39
8.4
135-145
294-314
4-9
7-12
9-11
19-25
163-173
365-385
11-16
4-9
7-9
33-39
4.9
139-149
418-438
4-9
10-15
14-16
17-23
7.0
139-149
398-418
4-9
9-14
10-12
17-23
8.4
139-149
390-410
4-9
8-13
8-10
17-23
Entering
Water Temp
°F
Water
Flow GPM
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
6.3
63-73
255-275
11-16
2-7
5-7
16-22
9.0
65-75
257-277
11-16
2-7
4-6
17-23
10.8
66-76
260-280
12-17
2-7
3-5
17-23
6.3
122-132
173-193
11-16
7-12
16-18
22-28
79-89
274-294
12-17
2-7
6-8
19-25
9.0
122-132
164-184
11-16
6-11
11-13
22-28
80-90
277-297
13-18
2-7
5-7
19-25
10.8
122-132
161-181
11-16
5-10
9-11
22-28
82-92
280-300
14-19
2-7
4-6
20-26
6.3
129-139
233-253
6-11
8-13
15-17
21-27
110-120
300-320
13-18
2-7
8-10
25-31
9.0
129-139
221-241
6-11
7-12
11-13
21-27
113-123
303-323
14-19
2-7
6-8
25-31
10.8
129-139
217-237
6-11
6-11
9-11
21-27
115-125
306-326
15-20
2-7
5-7
26-32
6.3
137-147
309-329
4-9
8-13
14-16
20-26
142-152
332-352
18-23
2-7
10-12
30-36
9.0
137-147
294-314
4-9
7-12
10-12
20-26
145-155
336-356
19-24
2-7
7-9
30-36
10.8
137-147
288-308
4-9
6-11
8-10
20-26
148-158
339-359
20-25
2-7
6-8
31-37
6.3
141-151
409-429
4-9
10-15
14-16
18-24
9.0
141-151
389-409
4-9
8-13
9-11
18-24
10.8
141-151
381-401
4-9
7-12
8-10
18-24
Entering
Water Temp
°F
Water
Flow GPM
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water Temp
Rise °F
Air DB Drop
°F
7.4
69-79
263-283
6-11
1-6
5-7
17-23
10.5
70-80
266-286
7-12
1-6
4-6
17-23
12.6
72-82
269-289
7-12
1-6
3-5
18-24
7.4
122-132
175-195
11-16
9-14
15-17
21-27
85-95
283-303
7-12
1-6
7-9
20-26
10.5
122-132
166-186
11-16
7-12
11-13
21-27
87-97
286-306
8-13
1-6
5-7
20-26
12.6
122-132
163-183
11-16
6-11
9-11
21-27
89-99
289-309
9-14
1-6
4-6
21-27
7.4
129-139
235-255
6-11
10-15
15-17
21-27
120-130
310-330
8-13
1-6
9-11
26-32
10.5
129-139
224-244
6-11
8-13
10-12
21-27
123-133
313-333
8-13
1-6
6-8
26-32
12.6
129-139
219-239
6-11
7-12
9-11
21-27
125-135
317-337
9-14
1-6
5-7
27-33
7.4
137-147
312-332
4-9
10-15
14-16
19-25
155-165
343-363
11-16
1-6
10-12
31-37
10.5
137-147
297-317
4-9
9-14
10-12
19-25
158-168
347-367
12-17
1-6
7-9
32-38
12.6
137-147
291-311
4-9
8-13
8-10
19-25
161-171
350-370
13-18
1-6
6-8
32-38
7.4
141-151
414-434
4-9
12-17
13-15
18-24
10.5
141-151
394-414
4-9
10-15
9-11
18-24
12.6
141-151
386-406
4-9
9-14
8-10
18-24
Vertical 030
Full Load Cooling
Full Load Heating
30
Out of Range
40
60
80
Vertical 042
Full Load Cooling
Full Load Heating
Out of Range
Vertical 036
Full Load Cooling
Full Load Heating
30
Out of Range
100
40
60
80
100
Out of Range
30
Out of Range
40
60
80
Out of Range
100