N
Horizontally from a terminal on the same wall.
300
R
From adjacent wall to flue (vertical only).
300
S
From an adjacent opening window (vertical only).
1000
T
Adjacent to windows or openings on pitched and flat roofs
600
U
Below windows or openings on pitched roofs
2000
1
In addition, the terminal should be no nearer than 150 mm to an opening in the building fabric formed for the purpose of accommodating a built-in element
such as a window frame.
2
Only
ONE
25mm clearance is allowed per installation. If one of the dimensions D, E, F, G or H is 25mm then the remainder
MUST
be as B.S.5440-1.
NOTE
: The distance from a fanned draught appliance terminal installed parallel to a boundary may not be less than 300mm in accordance with the diagram
below
Fig. 17a
Fig. 17