The construction of the framing, facing, and mantel must be in accordance with these guidelines and
illustrations.
FRAMING
ü
Frame the fireplace using 2” X 3” (50 X 75 mm) or heavier lumber.
ü
WARNING:
Combustible material cannot be placed behind the top standoffs of the fireplace. This
area must remain empty for a height of 7’ (2135 mm) measured from the base of the appliance. Frame
the fireplace with vertical studs at the sides of the fireplace running from floor to ceiling (SEE FIGURE
8). The enclosure can be framed prior to installation, allowing 42”(1067 mm) wide and 23” (584 mm)
deep (SEE FIGURE 8). If combustible facing is to be used, position the studs back from the front
edge of the fireplace and space the thickness of the facing material in order that the facing can be
installed flush with the fireplace facing. Combustible materials must not touch the unit.
ü
Frame headers between the vertical studs only as follows:
ü
Place 2” X 3” (50 X 75 mm) or 2” X 4” (50 X 100 mm) headers (SEE FIGURE 8) between the studs
only along the upper part of the front, side and back faces. Do not put wood or any combustible
material within the area behind the standoffs on top of the unit. This area is for venting and ductwork.
ü
Place headers only as required to support the facing and mantel, and place all headers on edge.
A
B
C
D
E
F
INCHES
41
83
41 1/2
59
26
22
MILLIMETER
S
1025
2075
1037.5
1475
650
550
FRAMING, FACING AND MANTEL