15
58-641 PULSAR Model R86 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
2.3.4 PULSAR Model R86 FF Device-Specific
Configuration Parameters
Refer to PULSAR Model R86 I/O Manual 58-603 for
detailed information on the Model R86 device-specific
configuration parameters.
2.4
Analog Input Block
The ANALOG INPUT (AI) block takes the PULSAR
Model R86 FF input data, selected by channel number, and
makes it available to other function blocks at its output.
The channel selections are:
2.4.1 AI Block Parameters
ST_REV
: : a read-only parameter that gives the revision
level of the static data associated with the block. This para-
meter will be incremented each time a static parameter
attribute value is written and is a vehicle for tracking
changes in static parameter attributes.
TAG_DESC
: a user assigned parameter that describes the
intended application of any given block.
STRATEGY:
a user assigned parameter that identifies
groupings of blocks associated with a given network
connection or control scheme.
ALERT_KEY
: a user-assigned parameter which may be
used in sorting alarms or events generated by a block.
Transducer
Blocks
Process Variable
Channel Parameter
Value
(AI Blocks)
TB1 – Level
Level
1
Distance
2
Echo Strength
3
Echo Margin
4
Electronics Temperature
5
TB2 – Volume
Volume
6
TB3 – Flow
and Totalizers
Flow
7
Head
8
NR Totalizer
9
R Totalizer
10