13
FD_RECOMMEN_ACT
: Describes what actions can be
taken to address an active diagnostic condition.
FD_EXTENDED_ACTIVE_1
: For error conditions that
have been selected in the Extended_Map_1 parameter, this
parameter reflects those that have been detected as active.
FD_EXTENDED_MAP_1
: Allows the user finer control
in selecting multiple conditions contributing to a single
condition that may be mapped for the various alarm
categories.
SERIAL_NUMBER
: Manufacturer specific read-only para-
meter that corresponds to “Magnetrol Serial Number” in
the Transducer Block.
SOFTWARE_REV
: Read-only parameter that corresponds
to “Firmware Version” in the Transducer Block.
HARDWARE_REV
: Read-only parameter that corresponds
to “Hardware Version” in the Transducer Block.
COMPATIBILITY_REV
: Read-only parameter that is
optionally used when replacing field devices. The correct
usage of this parameter presumes that the DEV_REV
value of the replaced device is equal or lower that the
COMPATIBILITY_REV value of the replacing device.
2.3
Transducer Block
The three TRANSDUCER blocks (TB) contained within
the PULSAR Model R86 FF transmitter are custom blocks
containing parameters pertinent to the transmitter itself.
TRANSDUCER Block 1 (used for level only operation)
contains information such as the Configuration, Diagnostics,
Calibration data, output level and Status information.
TRANSDUCER Block 2 contains parameters for volume
measurement configuration.
TRANSDUCER Block 3 contains parameters for flow mea-
surement calculations.
The read-only parameters and read-write parameters within
the TB are grouped in a useful configuration.
• The read-only parameters report the block status and
operation modes.
• The read-write parameters affect both the operation of
the function block and the transmitter itself.
NOTE: The Transducer Block will automatically be changed to “Out of
Service” when the local interface (keypad) is used to change a
static parameter online. The Transducer Block must be manually
placed back in service from the Host System to resume
operation.
58-641 PULSAR Model R86 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual