47
58-641 PULSAR Model R86 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
Refer to the table below for a complete listing of the Model
R86 diagnostic indicators, along with their explanations,
default categories, and recommended remedies.
NOTES: 1. The remedies shown in this table can also be seen on the
transmitter LCD by viewing the present status screen when
the device is in a diagnostic condition.
2. Those indicators showing failure as the default result in an
alarm condition.
5.1.2 Diagnostic Indication Simulation
The DD and DTM allow for the ability to manipulate
diagnostic indicators mapped to NE-107 alarm categories in
the Resource Block. Intended as a means to verify the con-
figuration of the diagnostic parameters and connected
equipment, a user can manually change any indicator in the
Resource Block to and from the active state.
5.1.3 Diagnostic Indicator Table
Below is a listing of the Model R86 diagnostic indicators,
showing their priority, explanations and recommended
remedies. (Priority 1 is highest priority.)
Priority
Indicator Name
Default
Category
Explanation
Remedy (Context Sensitive Help)
1
Software Error
Failure
Unrecoverable error occurred in stored
program
Contact MAGNETROL Technical Support
2
RAM Error
Failure
RAM (read/write) memory failing
3
ADC Error
Failure
Analog-to-digital converter failing
4
EEPROM Error
Failure
Non-volatile parameter storage failing
5
Analog Board
Error
Failure
Unrecoverable hardware failure
6
Spare Indicator
10
OK
Reserved for future use
7
Spare Indicator 1
OK
Reserved for future use
8
Default
Parameters
Failure
All saved parameters are set to default
values
Perform complete Device Setup
9
Spare Indicator 2
OK
Reserved for future use