12
FD_FAIL_MAP
: Maps conditions to be detected as active
for the FAIL alarm category.
FD_OFFSPEC_MAP
: Maps conditions to be detected as
active for the OFFSPEC alarm category.
FD_MAINT_MAP
: Maps conditions to be detected as
active for the MAINT alarm category.
FD_CHECK_MAP
: Maps conditions to be detected as
active for the CHECK alarm category.
FD_FAIL_MASK
: Used to suppress an alarm from being
broadcast for single or multiple conditions that are active in
the FAIL alarm category.
FD_OFFSPEC_MASK
: Used to suppress an alarm from
being broadcast for single or multiple conditions that are
active in the OFFSPEC alarm category.
FD_MAINT_MASK
: Used to suppress an alarm from
being broadcast for single or multiple conditions that are
active in the MAINT alarm category.
FD_CHECK_MASK
: Used to suppress an alarm from
being broadcast for single or multiple conditions that are
active in the CHECK alarm category.
FD_FAIL_ALM
: Used to broadcast a change in the associ-
ated active conditions, which are not masked, for the FAIL
alarm category.
FD_OFFSPEC_ALM
: Used to broadcast a change in the
associated active conditions, which are not masked, for the
OFFSPEC alarm category.
FD_MAINT_ALM
: Used to broadcast a change in the
associated active conditions, which are not masked, for the
MAINT alarm category.
FD_CHECK_ALM
: Used to broadcast a change in the
associated active conditions, which are not masked, for the
CHECK alarm category.
FD_FAIL_PRI
: Specifies the priority of the FAIL alarm
category.
FD_OFFSPEC_PRI
: Specifies the priority of the OFF-
SPEC alarm category.
FD_MAINT_PRI
: Specifies the priority of the MAINT
alarm category.
FD_CHECK_PRI
: Specifies the priority of the CHECK
alarm category.
FD_SIMULATE
: Diagnostic conditions can be manually
supplied when simulation is enabled.
58-641 PULSAR Model R86 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual