4.2.3 Dipswitch Settings
4.2.3.1 Interlocked Pushbutton Pair
Interlocked means any pushbutton pair cannot be
pressed simultaneously, as that pair will cancel the other
pair out. Interlocked setting usually applies to an
electric motor’s forward and reverse motion and On/Off
switches. Each dipswitch on the RF/decoder board
corresponds to a pushbutton pair.
Dip
Settings
Function Descriptions
# of Relays
Used
00000000
Single speed only
2
00000010
4 output relays Closed/Closed relay action at 2
nd
speed
(separate 2
nd
speed output relays)
4
00000100
3 output relays Closed/Closed relay action at 2
nd
speed
(shared 2
nd
speed output relay)
3
00000110
4 output relays Opened/Closed relay action at 2
nd
speed
(separate 2
nd
speed output relays)
4
00001000
Forward (or Reverse) + Fast output relays engaged at 2
nd
speed
4
00001010
Forward (or Reverse) + Slow + Fast output relays engaged at 2
nd
speed
4
00001100
On (right button) & Off (left button)
2
00010010
On + Start/Off + Start - For added safety, you must first
press and hold the START button and then press the
On or Off pushbutton to activate the output relay.
2
00010100
FWD/REV toggled (latching)
2
00100000
Single speed + External warning*
2
00100010
4 output relays Closed/Closed relay External warning*
4
00100100
3 output relays Closed/Closed relay External warning*
3
00100110
4 output relays Opened/Closed relay External warning*
4
01000010
4 output relays Closed/Closed relay Brake
4
01000100
3 output relays Closed/Closed relay Brake
3
01000110
4 output relays Opened/Closed relay Brake
4
01100010
4 output relays Closed/Closed relay Brake + External warning*
4
01100100
3 output relays Closed/Closed relay Brake + External warning*
3
01100110
4 output relays Opened/Closed relay Brake + External warning*
4
* External warning function requires installing an external warning device such as a horn and lights to the K26
Function output relay
.