21
21
70
5
30min
7days
3.0 Aux-heating
Parameter
3.4 Comp. Oil HT 5
3.5 Comp. Oil HT
T 5
3.6 Aux. start delay
30M
3.7 anti-virus
temp. 70
3.8 anti-virus time
30M
3.9 Anti-virus cycle time
period 7D
Start heating the compressor oil
temperature settings
shut off heating the compressor oil
temperature settings
Accumulated heat pump run time is
attained, the electric auxiliary allow start
High-temperature sterilization
temperature setting
High-temperature sterilization hold
time setting
High-temperature sterilization
cycle starts
0
--20
1
--20
2min
90min
60
-90
0min-240min
0days-14days
5
30min
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
*4.1 Run mode
A.C.-H.W./H.W./A.C.
4.2 Sys.Num. 1/2
*4.3 Heat pump Style
A.to W./W. to W.
4.4 HPPOT -15
4.5 A.to W.,
Fan on 50
4.6 A.to W.Fan
T 10
4.7 W .to W . pump
on 50
4.8 W.to W.
Pump
T 10
4.9 A.C. pump
Normal/Special
4.10 When
H.W.A.C.PM on
4.11 When A.C.3way. Off
4.0 Systems
Heat pump model settings
Single, double system options
Air source or water source options
Heat pump stoped working outside
temperature setting
Cooling and hot water mode, fan start
coil temperature
Cooling and hot water mode, stoped
fan coil temperature difference setting
Cooling and hot water mode, ground
source pump start inlet temperature setting
Cooling and hot water mode, ground
source pump stop inlet temperature
difference setting
When hot water reaches the set
temperature, set the pump mode.
Normal is stop;Special is working.
Hot water mode, the aircondition water
pump operating mode selection. On/off
Air conditioning heating mode,
the three-way valve mode selection.
A.C.-H.W./H.W./A.C.
1:single system
2:double system
A.to W./W. to W.
-50
- 50
30
125
1
50
2
99
10
30
Normal/Special
On/off
On/off
A.C.-H.W.
1
W.to W.
-15
48
10
Special
Off
Factory setting
Adjustable
Factory setting
Factory setting
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
10
48
Off
CLOCK
CLOCK
Date 2010-04-15
Clock 18:30
Timer on X
Timer off X
day setting
time setting
timer on setting
timer off setting
Adjustable
Adjustable
Adjustable
Adjustable
2
3.3 anti-virust
T 2
High-temperature sterilization auxiliary
heating start temperature difference setting
1
20
Adjustable
Display code1
Display code2
Setting data explanation or
working state
Parameter
setting range
Default
Remarks
*4.1.Heat pump model settings:A.C.-H.W.:air condition and hot water;H.W.:hot water;A.C.:air condition.
*4.3.A.to W.:air to water heat pump;W.to W.:water to water heat pump
5.1 Solar start
T 10
5.2 Solar stop
T 2
5.2 Solar heating Stop
hot water Temp. 75
5.0 Solar setting
Solar water pump start temperature
difference setting
Solar water pump stop temperature
difference setting
Solar water pump stopped working
tank temperature setting
1
20
1
20
10
2
Adjustable
Adjustable
Adjustable
6.0 pump testing
6.1 A.C. Pump on/off
6.2 Hot Water Pump
on/off
6.3 G.S. Water Pump
on/off
6.4 Solar Pump on/off
air condition pump on or off option
hot water pump on or off option
ground source pump on or off option
solar pump on or off option
Testing
Testing
Testing
Testing
1: E01 2010-01-14 09:00
2: P01 2010-01-14 09:10
3: E08 2010-01-14 09:30
4: E05 2010-01-14 09:40
5: P06 2010-01-14 09:50
6: P08 2010-01-14 10:00
Maintenance
Maintenance
60
90
75
On:running,off:stop
On:running,off:stop
On:running,off:stop
On:running,off:stop
4.12 Antifreezing 4
Ground source side antifreezing
protection temp. Setting
-20
10
4
Adjustable
Multi-Function Water To Water Heat Pump