9.Trial run
9

.1.Check the hot water side, air-conditioning side and solar side of the water system piping and  all accessories 

          are installed correctly, heat pumps, water tanks, terminal equipment piping connections are correct. The fill
          water supply of hot water side, air-conditioning side and solar side are normal, the replenishment port 
          whether installed pressure relief valve, one-way valve, filter and other accessories.
9.2.Open the unit hot water side, air-conditioning and solar side hydrating valve, circular inlet and outlet water 
          valve, main pipe backwater valve, floor branch pipe valve, terminal equipment inlet and outlet valve, fill the 
          hot water side water tank, air-conditioning side water tank and solar collector system with water. Check  the
           valves should be open if all open, the valves should be closed if all closed, pipe insulation if complete.
9.3.Open the exhaust valve, hot water valve, drain the pipe air, confirm pipe clean, close the exhaust valve, hot
       water valve.
9.4.Check the power supply if required with the unit power supply on the nameplate, power supply  voltage if 
       normal.
9.5.Check all power supply and control wires are all connected in place, whether connect  correctly according to
          the cable wiring diagram, all the terminals are tightened and check the reliability of ground connection.
9.6.Test Hot water side, air-conditioning side, solar side water system to test, first of all, heat pump units 
          connected to power supply, operating the remote controller (refer to the remote controller operation), start 
          the hot water side, air-conditioning side, solar side circulating pump, opened the exhaust valve again to drain
          the pipe air, observe and listen  water pump operation, the circulating water flow whether normal. Until the 
          hot water side, air-conditioning side, and solar side circulating water system work completely normal, close
          the hot water side, air conditioning and solar side circulating pump.     
9.7.When a full inspection of the entire system to install correctly and meet the requirements, may carry out the 
      whole test run.
9.8.Operate the unit controller, select the heat pump working mode and setting temperature, back to controller 
      main interface, press          

to start the heat pump.

9.9.First water pump operate 30s, the compressor starts. To determine unit operation if have different sound 
        through hearing, if is, shunt down power immediately and check, only continue running if there is no different 
        sound, at the same time pay attention to system high and low pressure if normal.
9.10.Check again whether the unit input power and current normal, if not, then shut down to check.
9.11 View the unit control operation status display, check and record the unit's output and input  status, the value
          of each point temperature indicated if normal.
9.12.Operate the unit controller, change the heat pump working mode, check and record the  unit's output and 
           input status, the value of each point temperature indicated if normal. Unit put into normal run only after 
        checking all the working modes are normal.

Note:

 

1          unit the first time power on without three minutes delay protection, other times there is three  minutes delay 
         protection.
2          must clean the pipe air when first the unit boot.

Multi-Function Water To Water Heat Pump

MACON

11

11

Содержание MWCRW045Z

Страница 1: ...Macon Cooling and Heating Energy efficient Equipment Co Ltd Macon Cooling and Heating Energy efficient Equipment Co Ltd MULTI FUNCTION WATER TO WATER MACON MACON...

Страница 2: ...nstallation diagram 6 Installation of the temp detector 7 Electrical wiring 8 Electrical Wire Selection 9 Trial run 10 IV Function diagram of the remote controller Controller parameter Table V Mainten...

Страница 3: ...the neutral and or tap water pipe 2 4 The wire must be joined in compliance with the requirements of the wiring chart Do not alternate and or repair the unit personally 2 5 The water temperature will...

Страница 4: ...mitted A Horizontal fan direction B Upward fan direction Design alternative serial number The figure represents the horse power of unit eg 010 means 1 horse power 4 Product work principle The dotted l...

Страница 5: ...ressor Compressor Qty Noise Water Flow Volume Water Pressure Drop Water Connection Water Flow Volume Water Pressure Drop Water Connection Water Flow Volume Water Pressure Drop Water Connection Refrige...

Страница 6: ...2 10 12 40 2 10 12 40 2 1500 980 1080 1600 1060 1220 400 450 450 500 250Z S 70 4 240200 91 5 312300 1875 23 20 22 04 40 7 38 7 380 3 50 3 0 0 05 Scroll 4 56 10 12 40 2 10 12 40 2 10 12 40 2 1500 980...

Страница 7: ...Dimensions Dimensions MACON MACON MACON Multi Function Water To Water Heat Pump 3 Product appearance and installation dimension 1 Installation dimensions of integrated type unit 5 5...

Страница 8: ...ing install the installation place is a solid foundation must be bear the weight of the tank when full of water 2 3 Around the water tank as well as water pipes and hot water pipes should install a va...

Страница 9: ...filter to reduce the water system resistance loss 5 7 The unit air conditioning side and the hot water side which connect to running water must be installed a one way valve filter and pressure relief...

Страница 10: ...ensure that the unit s maximum starting current requirements 7 3 The unit power supply circuit must have a grounding wire which should connect with a reliable external ground wire and the external gr...

Страница 11: ...line of board in the electrical box 7 8 Unit control panel Code MK3051 Fuse specifications 5A 250V 8 Electrical Wire Selection 8 1 Voltage drop occur may due to the large current draw during compress...

Страница 12: ...Z S 200Z S 200Z S 300Z S 450Z S 220V 1PH 50Hz 2 2 5mm 2 mm 380V 3PH 50Hz 2 2 5mm 2 mm 2 2 5mm 2 mm 2 2 5mm 2 mm 2 2 5mm 2 mm 2 2 5mm 2 mm 2 2 5mm 2 mm 2 2 5mm 2 mm 2 2 5mm 2 mm 2 2 5mm 2 mm 2 4 0mm 2...

Страница 13: ...art the hot water side air conditioning side solar side circulating pump opened the exhaust valve again to drain the pipe air observe and listen water pump operation the circulating water flow whether...

Страница 14: ...d be equipped with automatic exhausted valve which is in stalled at the highest of the water system refer to the pipe connection explanation The factory 12 12 Multi Function Water To Water Heat Pump M...

Страница 15: ...cle pump Hot water cycle pump Solar collector temperature sense Air condition electric heater temperature protect switch Mk3052 Controller Mk3051 Room 1 Turn ON OFF Room 2 Room N 220V 50HZ Electricity...

Страница 16: ...r Prg Prg Ese Ese UNIT ON OFF SET BACK UP DOWN ENTER Press this button to control the unit s ON or OFF Press this button to enter the main menu interface Press this button to return to the previous sc...

Страница 17: ...ating inlet temp Hot water mode Hot water temp H W Aux Heating A C Aux Heating Cooling 12 40 on 55 on off off Prg Prg Ese Ese Main menu Maintenance Clock Under the main interface press enter into para...

Страница 18: ...inlet G S water outlet 40 45 55 65 13 13 50 13 MACON Prg Prg Ese Ese H W aus Heater Comp Oil Heater 3 way valve on off on off on off Prg Prg Ese Ese A C flow sw G S flow sw H W flow sw Sys1 HP sw Sys...

Страница 19: ...e Ese 6 1 A C Pump 6 2 Hot Water Pump 6 3 G S Water Pump 6 4 Solar Pump on off on off on off on off Select Heat pump Select Defrost Select Aux heating Select Pump testing Select Systems Prg Prg Ese Es...

Страница 20: ...e value press the key again confirm and exit press the to return the layer menu Ese Ese 3 When you select Timer on press the key regular on or off setting flash press key to modify the boot time wheth...

Страница 21: ...lve on off Fan motor on off air condition cycle water pump on off Hot water cycle pump on off Solar cycle pump on off measured value measured value Actual state Actual state Actual state Actual state...

Страница 22: ...pump on off air condition cycle water pump on off Hot water cycle pump on off Solar cycle pump on off measured value measured value Actual state Actual state Actual state Actual state Actual state Act...

Страница 23: ...m 2 double system A to W W to W 50 50 30 125 1 50 2 99 10 30 Normal Special On off On off A C H W 1 W to W 15 48 10 Special Off Factory setting Adjustable Factory setting Factory setting Adjustable Ad...

Страница 24: ...is open or short circuit The sensor is open or short circuit The sensor is open or short circuit The sensor is open or short circuit The sensor is open or short circuit The sensor is open or short cir...

Отзывы: