19
19
MACON
A.C. mode
Cooling /Heating /Off
Cooling inlet temp. 12
Heating inlet temp. 40
Hot water mode on/off
Hot water temp. 55
H.W. Aux. Heating on/off
A.C. Aux. heating on/off
Priority hot water
/A. C. Heating/ATST
Cooling inlet temperature setting
Heating inlet temperature setting
hot water mode selection, on /off
Hot water temperature setting
Heating and hot water mode, the priority
selection.
hot water auxiliary eleceric heater on / off
settings
air condition auxiliary eleceric heater on /
off settings
Priority hot water:hot water priority
Priority A.C. Heating: air condiction priority
Priority ATST:air condiction and hot
water at the same time working
Hot water/A. C.
Heating/ATST
18
60
30
60
12
40
Off
ATST
Off
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Mode select
Main menu
8
18
Unit status
A.C. Inlet temp. 45
A.C. Outlet temp. 45
Hot water temp. 40
Rec. inlet temp. 65
air condition water inlet tempture
air condition water outlet tempture
tank hot water tempture
Heat recovery water inlet temperature
measured value
measured value
measured value
measured value
Sys1.Evap. temp. 13
Sys2.Evap. temp. 13
1 system evaporator coil temperature
(ground source water inlet temperature)
2 system evaporator coil temperature
(ground source water outlet temperature)
Solar temp. 50
Ambient temp. 13
Compressor 1 on/off
Compressor 2 on/off
4way-valve on/off
Fan motor on/off
A.C. water pump on/off
Hot water pump on/off
Solar pump on/off
Solar collector water temperature
Ambient temperature
1 system compressor on/off
2 system compressor on/off
4 way-valve on/off
Fan motor on/off
air condition cycle water pump on/off
Hot water cycle pump on/off
Solar cycle pump on/off
measured value
measured value
Actual state
Actual state
Actual state
Actual state
Actual state
Actual state
Actual state
measured value
measured value
A.C.aus. heater on/off
H.W. aus. Heater on/off
Comp. Oil Heater on/off
air condition auxiliary electric
heater on / off
hot water tempture auxiliary electric
heater on / off
compressor oil tempture auxiliary
electric heater on / off
3 way-valve on/off
3 way-valve on / off
air condition side water flow switch
close or open
ground source side water flow switch
close or open
hot water side water flow switch close
or open
1 system high pressure switch close
or open
1 system low pressure switch close
or open
2 system high pressure switch close
or open
2 system low pressure switch close
or open
Air-conditioning auxiliary electric heater,
thermal protection switch close or open
A.C. flow sw close/open
G.S. flow sw close/open
H.W. flow sw close/open
Sys1 HP sw close/open
Sys1 LP sw close/open
Sys2 HP sw close/open
Sys2 LP sw close/open
A.C. aux.TH sw close/open
H.W. Aus.TH sw close/open
Emergency Sw close/open
Phase sw close/open
Actual state
Actual state
Actual state
Actual state
Actual state
Actual state
Actual state
Actual state
Actual state
Actual state
Actual state
hot water auxiliary electric heater,
thermal protection switch close or open
Emergency Switch
close:working ;open:stop working
close:Normal; open:Phase, phase
sequence wrong.
Air to water
2. Controller parameter Table
Display code1
Display code2
Setting data explanation or
working state
Parameter
setting range
Default
Remarks
Cooling/heating/off
On/off
On/off
On/off
On
55
Cooling/heating/off
Heating
Multi-Function Water To Water Heat Pump