54
SC100/200 Series Function Block Application Manual EM-6460-C
■
CODING LIST ESSENTIALS
GROUP
ITEM
DATA
FUNCTION
02
10
37
38
39
2 2
1
3
3 0 2 1
Control block
Input compensation SW enabled
Input compensation method set to ‘substitution’
Input compensation connection terminal (multiplication block output)
30
10
11
12
13
5 2
7 2 2 1
0 2 2 3
1 . 0 0 0
Multiplication block
X1 connection terminal (linearizer block output)
X2 connection terminal (control block deviation output)
Gain K1
72
10
11
5 8
0 4 2 3
Linearizer block
X1 connection terminal (field terminal Ai 1)
[Linearization Data]
Set the output to 100% at the minimum gain within the input range (gain change factor). Set inverse to the gain at other input
points.
input (gain change factor)
gain
function
Loop gain can be maintained at a constant value
by setting the function to give [(gain)·(function) = 1].