SC100/200 Series Function Block Application Manual EM-6460-C
■
CODING LIST ESSENTIALS
GROUP
ITEM
DATA
FUNCTION
02
10
47
48
49
2 2
1
3
7 2 2 1
Control block
Output compensation SW enabled
Output compensation method set to ‘substitution’
Output compensation connection terminal (linearizer block output)
72
10
11
5 8
0 2 2 4
Linearizer block
X1 connection terminal (control block PID output)
21
22
:
:
:
:
36
s e t
s e t
:
:
:
:
s e t
A1 Input 1
B1 Output 1
:
:
:
:
B8 Output 8
Linearization data
[Linearization Data]
1) Manually operate the valve to determine a valve characteristics curve that correlates valve position and flow.
2) Divide the valve position axis into eight (8) divisions (do not need to be equal ones).
3) Read the gradient (gain) of the point closest to 0% (A1) and draw a line in its inverse gradient from 0% point to acquire
the B1 point.
4) Read the gradient of the A2 and draw a line in its inverse gradient from the B1 to acquire the B2.
5) Acquire all points in the same manner.
[Caution: Use of Output Compensation]
The MV output bumps when the control is switched from Man to Auto mode due to the ‘substitution’ type output compensation
employed by the controller.