10
SC100/200 Series Function Block Application Manual EM-6460-C
GROUP [04] SCxxx Extension Field Terminal 1
★
: Setting data
ITEM MDFY DATA INPUT
DISPLAY (e.g.) CONTENTS
10 IND 12
MD: 12
EXTENSION FIELD TERMINAL 1 (model)
ANALOG OUTPUT CONNECTION TERMINAL
★
25
▲
GGNN
M1#:
0225
Mv 1 connection terminal (error if not connected)
GG: Group No. NN : terminal No.
PV / MV SETTING
★
30
▲
-15.00 – 115.00 % PH1: 115.00
Pv 1 high alarm setpoint (for error judgment)
★
31
▲
-15.00 – 115.00 % PL1: -15.00
Pv 1 low alarm setpoint (for error judgment)
★
34
▲
0.00 – 115.00 %
ML1: 115.00
Mv 1 deviation alarm setpoint (for error judgment)
GROUP [02, 03] Basic PID
◆
: Automatically changeable parameters
★
: Setting data
ITEM MDFY DATA INPUT
DISPLAY (e.g.) CONTENTS
★
10
▲
21
MD:
21
BASIC PID (model)
‘-’ to clear.
PROCESS VALUE (PV)
★
15
▲
GGNN
P#:
0421
PV
connection
terminal
GG: Group No.
NN: terminal No.
◆
★
19
●
-15.00 – 115.00 % PH: 95.00
PV high alarm setpoint
◆
★
20
●
-15.00 – 115.00 % PL: 5.00
PV low alarm setpoint
◆
★
21
●
0.00 – 115.00 %
HS: 1.00
Hysteresis (deadband)
SETPOINT VALUE (SP)
★
24
▲
GGNN
(No connection)
CAS connection terminal
◆
★
27
●
-15.00 – 115.00 % SP: 50.00
Local SP %
★
29
▲
0, 1
SM: 0
Setting mode (0: local, 1: cascade/local)
DEVIATION
◆
★
34
●
0.00 – 115.00 %
DL: 115.00
Deviation alarm setpoint (hysteresis (deadband) in ITEM 21)
CONTROL
★
40
▲
0, 1
DR: 1
Control
direction
(0: direct, 1: reverse [MV decreases with PV increase])
★
41
▲
0, 1
DM: 0
Derivative method (0: PV derivative, 1: deviation derivative)
◆
★
42
●
1 – 1000 %
PB: 30
Proportional band
◆
★
43
●
0.00 – 100.00 min. TI: 2.00
Integral time (0: no integral action)
◆
★
44
●
0.00 – 10.00 min.
TD: 1.50
Derivative time (0: no derivative action)
★
45
▲
1, 2, 4, 8, 16, 32, 64 CP: 1
Control cycle (multiple of basic control cycle)
CONTROL OUTPUT MV
◆
★
50
●
±115.00 %
MH: 100.00
Output high limit
◆
★
51
●
±115.00 %
ML: 0.00
Output low limit
52
▲
0, 1
08: 0
Preset value SW (1: preset)
SUPERVISORY INDICATION USE
★
80
▲
alphanumeric
TG:
TIC-101
Tag name (10 characters max.)
★
81
▲
alphanumeric
TC:
TANK TEMP
Tag comment (16 characters max.)
★
82
▲
±32000
MH:
800
Upper range (in engineering unit)
★
83
▲
±32000
ML:
0
Lower range (in engineering unit)
★
84
▲
0, 1, 2, 3, 4, 5
DP: 1
Decimal point position (from rightmost digit)
★
85
▲
alphanumeric
TU:
C
Engineering unit (8 characters max.)
GROUP [81 – 92] Sequential Control Program
★
: Setting data
ITEM MDFY DATA INPUT
DISPLAY (e.g.) CONTENTS
★
10
▲
95
MD:
95
SEQUENTIAL CONTROL PROGRAM
(model) ‘-’ to clear.
★
11
▲
CCGGNN
010201
PV high alarm (Group 02, Terminal 01)
★
12
▲
CCGGNN
070501
Output at Do 1