MODBUS

ITEM

VALUE 

RANGE

INITIAL 

VALUE

PU-2x

R/W SAVE CFG

ADDRESS TYPE

ITEM

DISPLAY

43

I16

Time ratio (%) of 70 - 80% position  *

3

0.0 to 100.0

0.0

22

Pos70R:x

R

44

I16

Time ratio (%) of 80 - 90% position  *

3

0.0 to 100.0

0.0

23

Pos80R:x

R

45

I16

Time ratio (%) of 90%  - position  *

3

0.0 to 100.0

0.0

24

Pos90R:x

R

46

I16

Motor deadlock error

0: Normal
1: Locked when moving to full-open side
2: Locked when moving to full-close side

0 to 2

25

Lock:x

R

*2  The operation distance is a distance between the full-open position and the full-close position.
*3  The time ratio in percentage to the total operation time.

1.4.  Clear diagnostics

MODBUS

ITEM

VALUE 

RANGE

INITIAL 

VALUE

PU-2x

R/W SAVE CFG

ADDRESS TYPE

ITEM

DISPLAY

51

I16

Clear motor dead lock error
  1: Clear

0, 1

0

26

AccumClr:x R/W

52

I16

Time ratio (%) of respective % positions

 1: Clear

0, 1

0

27

PosRClr:x

R/W

1.5.  Modbus input

MODBUS

ITEM

VALUE 

RANGE

INITIAL 

VALUE

PU-2x

R/W SAVE CFG

ADDRESS TYPE

ITEM

DISPLAY

101

I16

Modbus position setpoint input (%)

-5.0 to 105.0

0

R/W

1.6.  Modbus operation mode

MODBUS

ITEM

VALUE 

RANGE

INITIAL 

VALUE

PU-2x

R/W SAVE CFG

ADDRESS TYPE

ITEM

DISPLAY

111

I16

Modbus operation mode
 (Forcibly returned to ‘0’ when SW1-8=ON)
  0: Monitor mode
  1: Modbus input mode
  2: Configuration mode

0 to 2

0

R/W

[0: Monitor mode]
· R/W registers of addresses up to 111 are readable and writable.
· Registers other than the above are read only.
[1: Modbus input mode]
· R/W registers of addresses up to 111 are readable and writable.
· Registers other than the above are read only.
· When [Input mode= Modbus input], the actuator operates according to [Modbus position setpoint input].
[2: Configuration mode]
· All R/W registers are readable and writable.
· Registers other than the above are read only.
· Operation stops.

Содержание MRP10

Страница 1: ...tem personnel Otherwise it could cause breakdown M System is not liable for any malfunction or inconven ience caused by unauthorized changes made by the user INSTRUCTION MANUAL This manual describes n...

Страница 2: ...line the temperature can rise higher than the ambient temperature due to heat con ducted through or radiated from the piping Use a longer yoke for effective heat dissipation and apply insulation mate...

Страница 3: ...ut Stem Packing Packing Terminal Block Wiring Conduits 4 G1 2 Transparent Cover Terminal Box Heater Figure 1 Component identification MRP10 PU 2x modular jack DIP Switch Manual Operation Buttons Confi...

Страница 4: ...with 20 mA DC input ON Direct Output stem moves to full close side with 20 mA DC input SW1 4 OFF Output signal is same as input signal ON Output signal is reversed input signal SW1 5 The output stem...

Страница 5: ...connected Also wire full open full close alarm and or output signals as necessary Modbus communication allows operation without analog input and monitoring of the operation status of the unit INPUT OU...

Страница 6: ...Operation angle can be adjusted by the UP CCW DOWN CW button Turn SW 8 from OFF to ON to enable manual operation If SW 8 is kept OFF control by input signal takes priority over Manual operation Adjus...

Страница 7: ...the actuator unit 3 To display a target item press ITEM then N N N represents numerical number 0 to 9 Alternatively use UP or DOWN button to shift to the next item from the currently displayed item 4...

Страница 8: ...table make sure to set Modbus Operation mode address 111 in advance to enable writing ADDRESS MAP Refer to PARAMETER ITEMS COMMON TO MODBUS CONFIGURATOR SOFTWARE AND PU 2x for Modbus address map DATA...

Страница 9: ...put 25 0 to 125 0 04 Inp x R 18 I16 Position setpoint 1 5 0 to 105 0 05 Tar x R 19 I16 Position 1 5 0 to 105 0 06 Pos x R 1 The ratio to the operation distance i e a distance between the lower stop po...

Страница 10: ...ISPLAY 51 I16 Clear motor dead lock error 1 Clear 0 1 0 26 AccumClr x R W 52 I16 Time ratio of respective positions 1 Clear 0 1 0 27 PosRClr x R W 1 5 Modbus input MODBUS ITEM VALUE RANGE INITIAL VALU...

Страница 11: ...settings of SW1 1 and 2 1 8 Basic setting MODBUS ITEM VALUE RANGE STANDARD EX FACTORY PU 2x R W SAVE ADDRESS TYPE ITEM DISPLAY 131 I16 Full open position degree 2 0 to 92 0 full close position 90 0 40...

Страница 12: ...de Stops Configuration mode Stops Modbus input Monitor mode Stops Modbus input mode Follows Modbus input Address 101 6 Configuration mode Stops ON N A 2 Monitor mode 4 Moves by button operation 1 Conf...

Страница 13: ...nt contact M System or our representatives LUBRICATION There is no need of oiling the Mini Top electronic actuator in normal operating conditions REGULAR TEST RUNNING If the valve is not frequently op...

Отзывы: