1.7.  Modbus setting

MODBUS

ITEM

VALUE 

RANGE

STANDARD

EX-FACTORY

PU-2x

R/W SAVE CFG

ADDRESS TYPE

ITEM

DISPLAY

121

I16

Input Select
  0: Analog input
  1: Modbus input 

0, 1

0

30

Inputsel:x R/W

122

I16

Node address

1 to 247

1

31

Addr:x

R/W

123

I16

Baud rate

 0: 38400 bps
 1: 19200 bps
 2: 9600 bps
 3: 4800 bps

0 to 3

3

32

Baud:x

R/W

124

I16

Parity
  0: None
  1: Odd
  2: Even

0 to 2

0

33

Parity:x

R/W

125

I16

Stop bit length

1, 2 

1

34

Stopbit:x

R/W

126

I16

Incorporated terminating resistor
  0: OFF
  1: ON

0, 1

0

35

Term:x:x

R/W

127

I16

Loss of Modbus communication detection 
time (sec.)

0 to 300

0

36

Timeout:x R/W

 

Description of Modbus setting

• Input select

  Set whether analog input or position output command viaModbus communication 

• Loss of Modbus communication detection time

  0: None
  1 to 300: Judges loss of communication when Modbus commands are not received for a set period of time or longer.
     

 

 If a loss of communication occurs during operation with Modbus input, the output stem moves according to the 

settings of SW1-1 and 2.

1.8.  Basic setting

MODBUS

ITEM

VALUE 

RANGE

STANDARD 

EX-FACTORY

PU-2x

R/W SAVE

ADDRESS TYPE

ITEM

DISPLAY

131

I16

Full-open position (degree)

-2.0 to 92.0

(> full-close 

position)

90.0

40

OpnDeg:x R/W

132

I16

Full-close position (degree)

-2.0 to 92.0

(> full-open 

position)

0.0

41

ClsDeg:x

R/W

133

I16

Deadband %

0.1 to 0.5

0.1

42

DBand:x

R/W

134

I16

Restart limiting timer (sec.)

0.1 to 5.0

0.1

43

Restart:x

R/W

135

I16

Full-open signal position %

75.0 to 100.0

98.0

44

OpnSig:x

R/W

136

I16

Full-close signal position %

0.0 to 25.0

2.0

45

ClsSig:x

R/W

137

I16

Operation speed

1 to 10

46

DBand:x

R/W

 

Description about basic setting

• Full-open / full-close position

  Set the output stem position at 100%/0% input.

• Deadband

  Set the deadband width with the stroke at the set full-open / full-close position as 100%.

• Restart limiting timer

  To prevent the overheat of the motor, set an interval to restart when the motor stops on the deadband.
  Using in a high-temperature atmosphere, set a longer restart limiting timer.

• Full-open / full-close signal position

  Set the threshold at which the full-open / full-close signal is turned ON with the stroke at the set full-open / full-close posi-

tion as 100%.

• Operation speed

  Set the operation speed on a scale of 1 to 10.  The higher the number, the faster the speed.
  Operation speed at the shipment is 10.

Содержание MRP10

Страница 1: ...tem personnel Otherwise it could cause breakdown M System is not liable for any malfunction or inconven ience caused by unauthorized changes made by the user INSTRUCTION MANUAL This manual describes n...

Страница 2: ...line the temperature can rise higher than the ambient temperature due to heat con ducted through or radiated from the piping Use a longer yoke for effective heat dissipation and apply insulation mate...

Страница 3: ...ut Stem Packing Packing Terminal Block Wiring Conduits 4 G1 2 Transparent Cover Terminal Box Heater Figure 1 Component identification MRP10 PU 2x modular jack DIP Switch Manual Operation Buttons Confi...

Страница 4: ...with 20 mA DC input ON Direct Output stem moves to full close side with 20 mA DC input SW1 4 OFF Output signal is same as input signal ON Output signal is reversed input signal SW1 5 The output stem...

Страница 5: ...connected Also wire full open full close alarm and or output signals as necessary Modbus communication allows operation without analog input and monitoring of the operation status of the unit INPUT OU...

Страница 6: ...Operation angle can be adjusted by the UP CCW DOWN CW button Turn SW 8 from OFF to ON to enable manual operation If SW 8 is kept OFF control by input signal takes priority over Manual operation Adjus...

Страница 7: ...the actuator unit 3 To display a target item press ITEM then N N N represents numerical number 0 to 9 Alternatively use UP or DOWN button to shift to the next item from the currently displayed item 4...

Страница 8: ...table make sure to set Modbus Operation mode address 111 in advance to enable writing ADDRESS MAP Refer to PARAMETER ITEMS COMMON TO MODBUS CONFIGURATOR SOFTWARE AND PU 2x for Modbus address map DATA...

Страница 9: ...put 25 0 to 125 0 04 Inp x R 18 I16 Position setpoint 1 5 0 to 105 0 05 Tar x R 19 I16 Position 1 5 0 to 105 0 06 Pos x R 1 The ratio to the operation distance i e a distance between the lower stop po...

Страница 10: ...ISPLAY 51 I16 Clear motor dead lock error 1 Clear 0 1 0 26 AccumClr x R W 52 I16 Time ratio of respective positions 1 Clear 0 1 0 27 PosRClr x R W 1 5 Modbus input MODBUS ITEM VALUE RANGE INITIAL VALU...

Страница 11: ...settings of SW1 1 and 2 1 8 Basic setting MODBUS ITEM VALUE RANGE STANDARD EX FACTORY PU 2x R W SAVE ADDRESS TYPE ITEM DISPLAY 131 I16 Full open position degree 2 0 to 92 0 full close position 90 0 40...

Страница 12: ...de Stops Configuration mode Stops Modbus input Monitor mode Stops Modbus input mode Follows Modbus input Address 101 6 Configuration mode Stops ON N A 2 Monitor mode 4 Moves by button operation 1 Conf...

Страница 13: ...nt contact M System or our representatives LUBRICATION There is no need of oiling the Mini Top electronic actuator in normal operating conditions REGULAR TEST RUNNING If the valve is not frequently op...

Отзывы: