MAINTENANCE

For effective use and longer life of the Mini-Top electronic actuator, regular checking appropriate for its operating conditions 
are recommended.  Refer to the following table.

ITEM

CHECKING POINT

HOW TO PROCEED

Stem operation

Apply input 0%, 50%, 100%, then back to 50%, 0%.
Check that the actuator operates to the correct posi-
tions at respective input values.

Repair or calibrate the unit.

Abnormal sound

No abnormal sound is heard during operation.

Repair or calibrate the unit.

Water or rust inside 
the housing

Check that there is no water or rust inside the hous-
ing.
If there is water inside, check the packing and the 
wiring cable connector is not loose.

Remove water and dry the housing and the parts 
inside.
Replace rusted parts, if any.
Replace the packing, if damaged.
Re-tighten cable connector, if loose.

Screws

Check that screws and bolts are securely fastened.

Re-tighten them, if loose.

For repair or parts replacement, contact M-System or our representatives.

 

LUBRICATION

There is no need of oiling the Mini-Top electronic actuator in normal operating conditions.

 

REGULAR TEST RUNNING

If the valve is not frequently operated, run a test operation regularly (once a week, for example) to ensure that the actuator 
operates normally.

TROUBLESHOOTING

TROUBLE

LED

POSSIBLE CAUSE

HOW TO PROCEED

POWER INPUT

COM

ALARM

Actuator does not 
work
(Analog input)

OFF

Power failure
Cable breakage

Check the power supply and cables.

ON

OFF

Input error

Check the input signal level.

ON

ON

Mode is set to Manual operation or 
Modbus input mode.

Check the operation mode.

ON

ON

ON Motor deadlock error

Apply input in reverse direction.

Actuator does not 
work
(Modbus input)

ON

OFF

Modbus communication is not established. Check the communication cable.

Check the Node address.
Check the baud rate.

ON

Blinks

Mode is set to Manual operation or 
Analog input mode.

Check the operation mode.

ON

ON Motor deadlock error

Clear error via Modbus.

Unstable operation

Abnormal power voltage,
Noise

Check power voltage and noise in 
input signal.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protec-
tors for protection against induced lightning surges. 

 

 

Please consult M-System to choose appropriate models.

Содержание MRP10

Страница 1: ...tem personnel Otherwise it could cause breakdown M System is not liable for any malfunction or inconven ience caused by unauthorized changes made by the user INSTRUCTION MANUAL This manual describes n...

Страница 2: ...line the temperature can rise higher than the ambient temperature due to heat con ducted through or radiated from the piping Use a longer yoke for effective heat dissipation and apply insulation mate...

Страница 3: ...ut Stem Packing Packing Terminal Block Wiring Conduits 4 G1 2 Transparent Cover Terminal Box Heater Figure 1 Component identification MRP10 PU 2x modular jack DIP Switch Manual Operation Buttons Confi...

Страница 4: ...with 20 mA DC input ON Direct Output stem moves to full close side with 20 mA DC input SW1 4 OFF Output signal is same as input signal ON Output signal is reversed input signal SW1 5 The output stem...

Страница 5: ...connected Also wire full open full close alarm and or output signals as necessary Modbus communication allows operation without analog input and monitoring of the operation status of the unit INPUT OU...

Страница 6: ...Operation angle can be adjusted by the UP CCW DOWN CW button Turn SW 8 from OFF to ON to enable manual operation If SW 8 is kept OFF control by input signal takes priority over Manual operation Adjus...

Страница 7: ...the actuator unit 3 To display a target item press ITEM then N N N represents numerical number 0 to 9 Alternatively use UP or DOWN button to shift to the next item from the currently displayed item 4...

Страница 8: ...table make sure to set Modbus Operation mode address 111 in advance to enable writing ADDRESS MAP Refer to PARAMETER ITEMS COMMON TO MODBUS CONFIGURATOR SOFTWARE AND PU 2x for Modbus address map DATA...

Страница 9: ...put 25 0 to 125 0 04 Inp x R 18 I16 Position setpoint 1 5 0 to 105 0 05 Tar x R 19 I16 Position 1 5 0 to 105 0 06 Pos x R 1 The ratio to the operation distance i e a distance between the lower stop po...

Страница 10: ...ISPLAY 51 I16 Clear motor dead lock error 1 Clear 0 1 0 26 AccumClr x R W 52 I16 Time ratio of respective positions 1 Clear 0 1 0 27 PosRClr x R W 1 5 Modbus input MODBUS ITEM VALUE RANGE INITIAL VALU...

Страница 11: ...settings of SW1 1 and 2 1 8 Basic setting MODBUS ITEM VALUE RANGE STANDARD EX FACTORY PU 2x R W SAVE ADDRESS TYPE ITEM DISPLAY 131 I16 Full open position degree 2 0 to 92 0 full close position 90 0 40...

Страница 12: ...de Stops Configuration mode Stops Modbus input Monitor mode Stops Modbus input mode Follows Modbus input Address 101 6 Configuration mode Stops ON N A 2 Monitor mode 4 Moves by button operation 1 Conf...

Страница 13: ...nt contact M System or our representatives LUBRICATION There is no need of oiling the Mini Top electronic actuator in normal operating conditions REGULAR TEST RUNNING If the valve is not frequently op...

Отзывы: