COMBINATION OF OPERATION MODE AND SPECIFICATIONS
OPERATION MODE
OPERATION SPECIFICATIONS
Manual
operation
Input
mode
(*1)
Modbus
operation mode
(*3)
Output stem operation
SW1-5, 6
PU-2x
Modbus
Retract (UP) /
Extend (DOWN)
Read data
/Clear data
command
Setting
change
Read data
/Clear data
command
(*7)
Setting
change
OFF
Analog
input
Monitor mode
Follows analog input (*5)
–
✓
–
✓
–
Modbus input mode
Stops
–
✓
–
✓
–
Configuration mode
Stops
–
✓
–
✓
✓
Modbus
input
Monitor mode
Stops
–
✓
–
✓
–
Modbus input mode
Follows
Modbus input
(Address 101) (*6)
–
✓
–
✓
–
Configuration mode
Stops
–
✓
–
✓
✓
ON
N/A
(*2)
Monitor mode
(*4)
Moves by
button operation
✓
✓
✓
✓
–
*1 Configurable on PU-2x (ITEM 30) or via Modbus (Address 121).
*2 No difference between ‘Analog input and ‘Modbus input’.
*3 The mode is switched via Modbus (address 111).
*4 Turn SW1-8 ON to forcibly switch the Modbus input mode to Monitor mode.
*5 The output stem operates according to the settings of SW1-1 and 1-2 when abnormally low input is detected.
*6 The output stem operates according to the settings of SW1-1 and 1-2 when a Modbus disconnection error is detected.
*7 Includes writing to Modbus address 5 to 16, 51, 52, 101, and 111.