MRP10

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-4889  P. 4 / 13

STATUS INDICATOR LED AND SIDE DIP SWITCH

 

STATUS INDICATOR LED

ID

COLOR

STATUS

FUNCTION

POWER

Green

ON

Power is ON.

INPUT

Green

ON

Position setpoint input (analog) of 0.37 V or greater is applied.
(With 250 Ω receiving resistor for current input)

AUTO-SETUP

MOVING UP/CCW

Green

ON

Output stem is moving up.

MOVING DOWN/CW

Green

ON

Output stem is moving down.

COM

Green

ON for 1 sec.

Returning response.

ALARM

Red

Blinks at 0.5 Hz

System error (memory)

ON

Motor deadlock alarm is output. 

Blink at 2 Hz

Motor is overheat.

 

SIDE DIP SWITCH SETTING

SW1

FUNCTION

SW1-1
SW1-2

Specify the operation of the output stem when abnormally low input is detected.
(INPUT LED is OFF).

SW1-1

SW1-2

Operation of the Output Stem

ON

Stop

OFF

OFF

Output stem stops at full-close position.

ON

OFF

Output stem stops at full-open position.

SW1-3

OFF

Reverse (Output stem moves to full-open side with 20 mA DC input)

ON

Direct (Output stem moves to full-close side with 20 mA DC input)

SW1-4

OFF

Output signal is same as input signal.

ON

Output signal is reversed input signal.

SW1-5

The output stem position when the switch is turned OFF is recorded as the full-open position.

SW1-6

The output stem position when the switch is turned OFF is recorded as the full-close position.

SW1-7

SW1-8

OFF

Automatic operation 
(Operation is performed based on input signal or Modbus)

ON

Manual operation
(Manual operation buttons are enabled.)

 

MANUAL OPERATION BUTTON

ID

FUNCTION

UP/CCW

The output stem turns left to full-open side in Manual Operation mode as the button is pressed.
(Viewing from the top of the cover.)

DOWN/CW

The output stem turns right to full-close side in Manual Operation mode as the button is pressed.
(Viewing from the top of the cover.)

 

USB Type-C

Connecting the MRP and the PC via USB Type-C cable and using the PC configurator software, various settings and monitor-
ing operation status can be performed.

 

PU-2X MODULAR JACK

Parameter settings for Auto-setup and communication settings for Modbus can be configured on PU-2x. 
In addition, operation status of the unit can be monitored on PU-2x.

Содержание MRP10

Страница 1: ...tem personnel Otherwise it could cause breakdown M System is not liable for any malfunction or inconven ience caused by unauthorized changes made by the user INSTRUCTION MANUAL This manual describes n...

Страница 2: ...line the temperature can rise higher than the ambient temperature due to heat con ducted through or radiated from the piping Use a longer yoke for effective heat dissipation and apply insulation mate...

Страница 3: ...ut Stem Packing Packing Terminal Block Wiring Conduits 4 G1 2 Transparent Cover Terminal Box Heater Figure 1 Component identification MRP10 PU 2x modular jack DIP Switch Manual Operation Buttons Confi...

Страница 4: ...with 20 mA DC input ON Direct Output stem moves to full close side with 20 mA DC input SW1 4 OFF Output signal is same as input signal ON Output signal is reversed input signal SW1 5 The output stem...

Страница 5: ...connected Also wire full open full close alarm and or output signals as necessary Modbus communication allows operation without analog input and monitoring of the operation status of the unit INPUT OU...

Страница 6: ...Operation angle can be adjusted by the UP CCW DOWN CW button Turn SW 8 from OFF to ON to enable manual operation If SW 8 is kept OFF control by input signal takes priority over Manual operation Adjus...

Страница 7: ...the actuator unit 3 To display a target item press ITEM then N N N represents numerical number 0 to 9 Alternatively use UP or DOWN button to shift to the next item from the currently displayed item 4...

Страница 8: ...table make sure to set Modbus Operation mode address 111 in advance to enable writing ADDRESS MAP Refer to PARAMETER ITEMS COMMON TO MODBUS CONFIGURATOR SOFTWARE AND PU 2x for Modbus address map DATA...

Страница 9: ...put 25 0 to 125 0 04 Inp x R 18 I16 Position setpoint 1 5 0 to 105 0 05 Tar x R 19 I16 Position 1 5 0 to 105 0 06 Pos x R 1 The ratio to the operation distance i e a distance between the lower stop po...

Страница 10: ...ISPLAY 51 I16 Clear motor dead lock error 1 Clear 0 1 0 26 AccumClr x R W 52 I16 Time ratio of respective positions 1 Clear 0 1 0 27 PosRClr x R W 1 5 Modbus input MODBUS ITEM VALUE RANGE INITIAL VALU...

Страница 11: ...settings of SW1 1 and 2 1 8 Basic setting MODBUS ITEM VALUE RANGE STANDARD EX FACTORY PU 2x R W SAVE ADDRESS TYPE ITEM DISPLAY 131 I16 Full open position degree 2 0 to 92 0 full close position 90 0 40...

Страница 12: ...de Stops Configuration mode Stops Modbus input Monitor mode Stops Modbus input mode Follows Modbus input Address 101 6 Configuration mode Stops ON N A 2 Monitor mode 4 Moves by button operation 1 Conf...

Страница 13: ...nt contact M System or our representatives LUBRICATION There is no need of oiling the Mini Top electronic actuator in normal operating conditions REGULAR TEST RUNNING If the valve is not frequently op...

Отзывы: