Section 6: Installation
P a g e | 19
6.5.3 Chemical Level Switches
The
Easyzon D
has two empty level switch inputs
located on its control panel, see
[10]
&
[11]
on
diagrams in section 4.2. They are male 4-pin M12
Code A connections, see diagram below for pin
configuration.
Installation steps:
1.
Check that the pins allocated for the empty
level switch on the lances match up with the
pins on the
Easyzon D
switch inputs (Diagram
below).
2.
Plug the M12 connector from your acid suction
switch into the left-hand side receptacle on the
control panel.
3.
Plug the M12 connector from your chlorite
suction switch into the right-hand side
receptacle on the control panel.
4.
Enable the Acid Empty and Chlorite Empty
alarms in the
Easyzon
software (program 10 &
11
respectively).
✓
Suction level switch installation complete
Note:
•
This switch is a N.C contact, take note of float
positions on lances (see section 6.4.3).
•
For assistance in software navigation see
section 8.
6.5.4 Site Water Meter
A water meter can be connected to the
Easyzon D
system to enable local readings through the control
panel display, and remote readings via the
communications box (Optional accessory).
Installation Steps:
1.
Isolate power to the system.
2.
Select a suitable size cable entry insert from the
kit provided (see section 6.3).
3.
Run the cable from the meter through the
Easyzon D
cable entry system.
4.
Wire the meter into the
Easyzon D
control panel
using
the electrical diagram (see section 6.5.2).
5.
Set up K factor and current water meter reading
(see section 8.4.3).
✓
Site water meter electrical installation
complete.
6.5.5 Auxiliary Alarm Input
Apparatus with a normally closed volt free alarm output
can be connected into the
Easyzon D
PCB, to halt the
systems operation in the event of an external alarm
state. E.g. A chlorine dioxide gas sensor reaching its
upper limit and activating a relay output.
Installation Steps:
1.
Isolate power to the system.
2.
Select a suitable size cable entry insert from the
kit
provided (see section 6.3).
3.
Run the cable from the N.C external alarm
contact through the
Easyzon
cable entry system.
4.
Wire into the
Easyzon D
control panel using
the
electrical diagram (see section 6.5.2).
5.
Enable the auxiliary alarm option at Program 13
in
the
Easyzon D
software.
✓
Auxiliary alarm installation complete.
Note:
•
For assistance in software navigation see
section 8.
•
Damage may occur if an external voltage is
applied to the PCB terminals.
6.5.6 Remote Inhibit
The operation of the
REasyzon D
can be inhibited via
external switching if a control process requires it. A
volt free contact is used and is normally closed
in healthy operation.
Installation Steps:
1.
Isolate power to the
Easyzon D
.
2.
Select a suitable size cable entry insert from the
kit provided (see section 6.3).
3.
Run the cable from the external switch through
the
Easyzon D
cable entry system.
4.
Wire into the
Easyzon D
control panel using
the
electrical diagram (see section 6.5.2).
5.
Enable the Remote Inhibit option at Program 14
in the
Easyzon D
software.
✓
Remote Inhibit feature installation complete
Note:
•
For assistance in software navigation see
section 8.
•
Damage may occur if an external voltage is
applied to the PCB terminals.
6.5.7 Gas Sensor
A gas warning device is recommended for use with the
Easyzon D
see
your
device
manual
for
instructions. If you wish to use your gas sensing
apparatus to inhibit the
Easyzon D
when an alarm state
occurs, see section 6.5.5.
Содержание Easyzon D 100
Страница 2: ...This page is left intentionally blank...
Страница 10: ...Section 3 Technical Data P a g e 7 3 2 Dimensions 3 2 1 Easyzon D Skid dimensions...
Страница 17: ...Section 6 Installation P a g e 1 4...
Страница 21: ...Section 6 Installation P a g e 18 6 5 2 Field Wiring Diagram Easyzon D PCB Iss 4 electrical diagram...
Страница 45: ......