background image

Wallbox Power Module Installation and Operation Guide   8

®

DALI Setup

After DALI

 

devices are wired and powered, they must be addressed before the 

system can control them. The “Build System” command automates this process.

Note:

  All existing DALI

 

programming will be deleted when the “Build System” 

command is run, including DALI

 

sensor programming on the Wallbox Power 

Module control unit.

Building the System

1.  Enter programming mode by pressing and holding the OK 

button and timeclock (back) button for 3 seconds.

2.  Use the Master buttons to highlight “DALI” and press the OK 

button to accept.

3.  Use the Master buttons to highlight “Build system” and press 

the OK button to accept.

4.    Press the OK button to erase all current programming, reset 

and address DALI devices, and find sensors on the system. 

5.  Exit programming mode.
 

Note:

  After running “Build System”, Zone 4 will control all DALI 

devices for diagnostics and verification of wiring. (This 

feature is disabled once any of the addressed devices 

are assigned to a zone on the Wallbox Power Module 

control unit.) Use the Zone 4 raise/lower buttons to verify 

that all devices are correctly addressed. If a device does 

not respond, repeat the “Build System” command and/

or check the wiring.

Main menu

Zone setup

DALI

Assign zones

Build system

Erase digital load

Programming?

Build system

DALI

OK

1

2

3

4

5

6

9

10

11

12

13

14

7

8

15

16

9-16

1-8

Use Zone 4 

raise/lower 

buttons 

to verify 

all DALI 

devices 

have been 

addressed.

Searching...

x

Found

x Loads

Found

OK

1

2

3

4

5

6

9

10

11

12

13

14

7

8

15

16

9-16

1-8

Master 

buttons

OK  

button

Timeclock 

(back) button

Содержание LQR-WPM-16D

Страница 1: ...mbers Ratings 120 240 V 50 60 Hz 100 mA 230 V 50 60 Hz 100 mA Typical Power Consumption 7 W 24 BTUs Power Draw Units PDUs 0 Output DALI Link 18 V 250 mA Codes Install in accordance with all applicable...

Страница 2: ...age terminal can accept one 4 0 mm2 wire Consult Lutron for non dim relay wiring and or load side emergency transfer wiring D1 D1 D2 D2 1 2 3 4 5 6 L N 1 2 3 4 5 6 L N Wiring the Wallbox Power Module...

Страница 3: ...WARNING Shock hazard May result in serious injury or death Always turn off circuit breaker or remove main fuse from power line before doing any work Step 3 Connect line voltage and loads to control u...

Страница 4: ...e live Always turn off circuit breaker or remove main fuse from power line before wiring and servicing the Wallbox Power Module Step 1 Use the wire size chart at right to determine which wire size to...

Страница 5: ...use from power line before doing any work Step 1 Strip 25 mm of insulation from the IEC PELV NECR Class 2 cable Step 2 Strip 7 mm of insulation from each wire in the cable Step 3 Connect the wires to...

Страница 6: ...e on rest the top of the wallplate in the grooves at the top of the unit and press firmly at the bottom corners to secure Step 4 Turn on circuit breaker and check that it does not trip For any feed ci...

Страница 7: ...ou to move through the menu choices The current choice is highlighted on the info screen OK Button The OK button chooses the current highlighted menu choice This will either take you to the next menu...

Страница 8: ...tton to erase all current programming reset and address DALI devices and find sensors on the system 5 Exit programming mode Note After running Build System Zone 4 will control all DALI devices for dia...

Страница 9: ...display at the bottom of the screen and the LEDs for the zone will go on otherwise the info screen will display Unassigned Press the zone raise button to assign the device to that zone Press the zone...

Страница 10: ...he OK button to accept 3 Use the Master buttons to highlight Address All and press the OK button to accept All DALI devices in the system will go to full On As each DALI device is addressed the Wallbo...

Страница 11: ...the third tap Step 2 Keep the Default Scene Button pressed on the third tap for approximately 3 seconds until the LED flashes slowly Step 3 Release the Default Scene Button and immediately triple tap...

Страница 12: ...and shorts HomeWorksR QS only Device is in the Factory Default Settings mode and has not been activated into the system Use the system software to verify activation or reactivate the device and transf...

Отзывы: