Wallbox Power Module Installation and Operation Guide   12

Troubleshooting Guide

Symptom

Probable Cause

Solution

Unit does not power up

- Power is not present at module

•  Circuit Breaker is OFF or tripped

- Miswire

•  Verify wiring to unit and loads

•  Locate and correct shorts

Lights don’t switch ON/OFF when the Default Scene Button 

is pressed

- Miswire

•  Verify loads are connected to the correct outputs

•  Verify loads wiring matches wiring diagrams

- Lamps burned out or not installed

•  Replace or install lamps

Lights don’t switch ON/OFF from a keypad

- Verify that other lights or system devices respond to that keypad

- Keypad is not in HomeWorks

R

 QS or RadioRA

R

 2 system

•  If not, the issue may not be with the unit but may be the keypad 

or system programming

-  Device is not communicating with the system  

—  Use the communication diagnostics tool in the system software 

to help troubleshoot device communication issues

•  Device is configured as an RF device and it is out of range of an 

RF signal repeater

•  Device is configured as a wired, QS device. Verify the QS 

link wiring is correct including loose conductors and shorts 

(HomeWorks

R

 QS only)

•  Device is in the Factory Default Settings mode and has not been 

activated into the system. Use the system software to verify 

activation or reactivate the device and transfer its database

- Device is not properly programmed

•  Program or verify the programming using the system software

“Build System” command does not find DALI loads

- D1 and /or D2 are miswired or not connected

• Check wiring; if wiring is correct, call Lutron

R

 Technical Support

Cannot add a DALI device to a zone after a “Build System” 

or “Address All” command has been run

- Zone is not set to "Digital"

• Set the zone to "Digital"

DALI device at full brightness cannot be controlled

- D1 and D2 are not connected

•  Check D1 and D2 connections on the back of the WPM with DALI 

control unit

- DALI link is overloaded

• Reduce number of DALI devices on link to 64 or fewer

• Check voltage: Minimum voltage of 12 V

-

DALI devices do not flash when running the “Build System” 

command

- DALI devices are not addressed

• Address DALI devices

- DALI devices are miswired

• Check D1 and D2 wiring, and power wiring to DALI devices

DALI device is not affected by a zone level change

- DALI device is not addressed

• Run the “Address All” command and assign the DALI device to a zone

- DALI device is not assigned to a zone

• Assign DALI device to a zone

Содержание LQR-WPM-16D

Страница 1: ...mbers Ratings 120 240 V 50 60 Hz 100 mA 230 V 50 60 Hz 100 mA Typical Power Consumption 7 W 24 BTUs Power Draw Units PDUs 0 Output DALI Link 18 V 250 mA Codes Install in accordance with all applicable...

Страница 2: ...age terminal can accept one 4 0 mm2 wire Consult Lutron for non dim relay wiring and or load side emergency transfer wiring D1 D1 D2 D2 1 2 3 4 5 6 L N 1 2 3 4 5 6 L N Wiring the Wallbox Power Module...

Страница 3: ...WARNING Shock hazard May result in serious injury or death Always turn off circuit breaker or remove main fuse from power line before doing any work Step 3 Connect line voltage and loads to control u...

Страница 4: ...e live Always turn off circuit breaker or remove main fuse from power line before wiring and servicing the Wallbox Power Module Step 1 Use the wire size chart at right to determine which wire size to...

Страница 5: ...use from power line before doing any work Step 1 Strip 25 mm of insulation from the IEC PELV NECR Class 2 cable Step 2 Strip 7 mm of insulation from each wire in the cable Step 3 Connect the wires to...

Страница 6: ...e on rest the top of the wallplate in the grooves at the top of the unit and press firmly at the bottom corners to secure Step 4 Turn on circuit breaker and check that it does not trip For any feed ci...

Страница 7: ...ou to move through the menu choices The current choice is highlighted on the info screen OK Button The OK button chooses the current highlighted menu choice This will either take you to the next menu...

Страница 8: ...tton to erase all current programming reset and address DALI devices and find sensors on the system 5 Exit programming mode Note After running Build System Zone 4 will control all DALI devices for dia...

Страница 9: ...display at the bottom of the screen and the LEDs for the zone will go on otherwise the info screen will display Unassigned Press the zone raise button to assign the device to that zone Press the zone...

Страница 10: ...he OK button to accept 3 Use the Master buttons to highlight Address All and press the OK button to accept All DALI devices in the system will go to full On As each DALI device is addressed the Wallbo...

Страница 11: ...the third tap Step 2 Keep the Default Scene Button pressed on the third tap for approximately 3 seconds until the LED flashes slowly Step 3 Release the Default Scene Button and immediately triple tap...

Страница 12: ...and shorts HomeWorksR QS only Device is in the Factory Default Settings mode and has not been activated into the system Use the system software to verify activation or reactivate the device and transf...

Отзывы: