Wallbox Power Module Installation and Operation Guide   4

•  DALI terminal block is double insulated 

from QS and mains voltage terminals.

•  DALI bus wiring may be run in the same 

conduit as mains wiring.

• Lutron recommends using two different 

colors for D1 and D2 (DALI

 

bus) wires. 

This will prevent wiring mistakes in 

junction boxes where several different 

DALI

 

bus

 

wires combine. Use the 

following instructions for wiring the DALI

 

bus.

• Each DALI bus

 

link can have only 1 

Wallbox Power Module (WPM) with DALI 

control unit connected to it. No additional 

DALI supplies can be on the link.

• Up to 64 DALI devices can be connected 

to the DALI bus.

• No other devices may be connected to 

the DALI

 

link.

WARNING! Shock hazard. 

May result in serious injury or 

death. 

Do not wire live. Always 

turn off circuit breaker or remove 

main fuse from power line before 

wiring and servicing the Wallbox 

Power Module.

  Step 1: 

Use the wire size chart at right to 

determine which wire size to use based 

on the length of the DALI

 

bus.

 

Step 2: 

Wire the DALI

 

bus from terminal 

D1 and terminal D2 to all DALI devices.

 

Step 3: 

Turn on circuit breaker to 

energize. 

DALI Bus
18 V

-

250 mA

Wiring the Wallbox Power Module with DALI Control Unit:
DALI-Compliant

 

Bus Wiring Details

Wiring Size and Bus Length

DALI

 

bus wires D1 and D2 are not 

polarity sensitive. DALI bus length is 

limited by the wire gauge used for D1 and 

D2 as follows:

Wire Gauge

Maximum DALI 
Bus Length

1.5 mm

2

300 m

0.75 mm

2

150 m

0.50 mm

2

100 m

Note:

   Some  DALI

 

devices

 

(ballasts, 

drivers, and interfaces) accept 

connections to daylight sensors 

and occupancy sensors. For 

instructions on installing and 

operating these devices, refer to 

their individual instruction sheets.

ON

OFF

ON

OFF

ON

OFF

Содержание LQR-WPM-16D

Страница 1: ...mbers Ratings 120 240 V 50 60 Hz 100 mA 230 V 50 60 Hz 100 mA Typical Power Consumption 7 W 24 BTUs Power Draw Units PDUs 0 Output DALI Link 18 V 250 mA Codes Install in accordance with all applicable...

Страница 2: ...age terminal can accept one 4 0 mm2 wire Consult Lutron for non dim relay wiring and or load side emergency transfer wiring D1 D1 D2 D2 1 2 3 4 5 6 L N 1 2 3 4 5 6 L N Wiring the Wallbox Power Module...

Страница 3: ...WARNING Shock hazard May result in serious injury or death Always turn off circuit breaker or remove main fuse from power line before doing any work Step 3 Connect line voltage and loads to control u...

Страница 4: ...e live Always turn off circuit breaker or remove main fuse from power line before wiring and servicing the Wallbox Power Module Step 1 Use the wire size chart at right to determine which wire size to...

Страница 5: ...use from power line before doing any work Step 1 Strip 25 mm of insulation from the IEC PELV NECR Class 2 cable Step 2 Strip 7 mm of insulation from each wire in the cable Step 3 Connect the wires to...

Страница 6: ...e on rest the top of the wallplate in the grooves at the top of the unit and press firmly at the bottom corners to secure Step 4 Turn on circuit breaker and check that it does not trip For any feed ci...

Страница 7: ...ou to move through the menu choices The current choice is highlighted on the info screen OK Button The OK button chooses the current highlighted menu choice This will either take you to the next menu...

Страница 8: ...tton to erase all current programming reset and address DALI devices and find sensors on the system 5 Exit programming mode Note After running Build System Zone 4 will control all DALI devices for dia...

Страница 9: ...display at the bottom of the screen and the LEDs for the zone will go on otherwise the info screen will display Unassigned Press the zone raise button to assign the device to that zone Press the zone...

Страница 10: ...he OK button to accept 3 Use the Master buttons to highlight Address All and press the OK button to accept All DALI devices in the system will go to full On As each DALI device is addressed the Wallbo...

Страница 11: ...the third tap Step 2 Keep the Default Scene Button pressed on the third tap for approximately 3 seconds until the LED flashes slowly Step 3 Release the Default Scene Button and immediately triple tap...

Страница 12: ...and shorts HomeWorksR QS only Device is in the Factory Default Settings mode and has not been activated into the system Use the system software to verify activation or reactivate the device and transf...

Отзывы: