![Lucent Technologies Stinger FS Скачать руководство пользователя страница 80](http://html.mh-extra.com/html/lucent-technologies/stinger-fs/stinger-fs_getting-started-manual_1946211080.webp)
5-14
Stinger® FS/Stinger FS+ Getting Started Guide
Configuring Control Modules and System Timing
Providing a basic system IP configuration
Figure 5-6. Local backbone router to be used as default route
If a local router is the unit’s default route, or gateway, the Stinger unit can pass all IP
packets with an unrecognized address to that router, so its own routing table can
remain small. The external router maintains larger routing tables and assumes the
responsibility and overhead of routing most packets.
For example, the following commands define a default route to the LAN router in
Figure 5-6:
admin>
new
ip-route default
IP-ROUTE/default read
admin>
set gateway-address = 1.1.1.3
admin>
set active-route = yes
admin>
write
IP-ROUTE/default written
The system can support multiple default routes. The profile name does not have to be
default
. The only requirements are that the destination address must be zero, and
Gateway-Address must specify a valid, accessible router.
For information about other settings in the IP-Route profile, see the
Stinger Reference
.
Verifying a LAN connection for administrators
To enable administrators to log into the Stinger unit’s interface from IP hosts, you
must also make sure your local network can route to the unit. Your network router
must have network connectivity through intermediate routers so that the
administrative host can access the Stinger unit via its IP address. You can test this
connectivity by pinging the unit from the local host. For example, the following
command entered on a local host tests connectivity to the Stinger soft interface,
identified previously:
%
ping 1.1.1.128
PING 1.1.1.128 (1.1.1.128): 56 Data bytes
64 bytes from 1.1.1.128: icmp_seq=0 ttl=255 time=0 ms
64 bytes from 1.1.1.128: icmp_seq=7 ttl=255 time=0 ms
^C
--- 1.1.1.128 Ping statistics ---
8 packets transmitted, 8 packets received, 0% packet loss
round-trip min/avg/max = 0/0/0 ms
Secondary control module’s
Ethernet port
Primary control module’s
Ethernet port
1.1.1.1/24
1.1.1.2/24
Hub
1.1.1.3/24
1.1.2.3/24
Local