Stinger® FS/Stinger FS+ Getting Started Guide
3-1
3
Determining the Operating
Status
Before you begin
Before you begin, verify that the following tasks are complete:
■
Set up the Stinger hardware (as either a free-standing or rack-mounted unit)
■
Connected cables and console terminal to the Stinger unit
■
Set up the workstation to configure the Stinger unit
■
Connected the workstation to the Stinger unit
■
(Optional)
Connected the system clock source
■
(Optional)
Connected the remote alarms
Evaluating power consumption
Table 3-1 identifies the power consumption of each Stinger component to help you
determine the current and power required for the unit.
Table 3-1. Stinger component power requirements
Stinger component
dc amps per
component
(48Vdc)
Watts per
component
Base system (one standard control
module and fan)
2.80
134.40
Redundant standard control module
0.78
37.44
IP2000 IP control module
1.46
70 (maximum)
IP2100 IP control module
1.46 70
(maximum)