Lucent Technologies ECS Minicell Battery Plant H569-420
Issue 5 February 1997
Maintenance 7 - 7
3. Disconnect and label the 5 quick connects from the
contactor coil and auxiliary switch.
4. Unbolt and remove contactor.
5. Reconnect quick connect leads to the new contactor
(406545442 JFA-4011B Contactor) and then mount the
contactor using the hardware from Step 4.
6. Plug P501 into J501 on LVD/Fuse board and verify that
contactor closes.
7. Replace rectifier and turn on.
8. Close distribution panel and verify that LVD FAIL and
LVD OPEN lights are not lit.
LVD/Fuse Board
(CP5)
Replacement
Refer to Figure 5-4 and T-83260-30 drawing throughout this
procedure.
1. Open distribution panel.
2. Unplug the following connectors from the LVD/Fuse
Board. Leave the cables dressed.
•
P502 from J502
•
P506 from J506
•
P501 from J501
•
P504 from J504
•
TB501
3. Remove the cover over the LVD/Fuse Board and then
remove the insulated standoffs to free the board.
4. Set jumpers J505.1 and J505.2 on replacement LVD/Fuse
Board per H569-420 drawing for desired disconnect
voltage.
5. Mount the replacement board to the distribution panel
using the hardware from Step 3.
6. Reconnect the following connectors:
Note
The contactor will open.
Содержание H569-420
Страница 2: ......
Страница 7: ...Lucent Technologies ECS Minicell Battery Plant H569 420 2 List of Figures Issue 5 February 1997 ...
Страница 15: ...Lucent Technologies ECS Minicell Battery Plant H569 420 1 6 Introduction Issue 5 February 1997 ...
Страница 71: ...Lucent Technologies ECS Minicell Battery Plant H569 420 6 8 Installation Tables Issue 5 February 1997 ...
Страница 81: ...Lucent Technologies ECS Minicell Battery Plant H569 420 8 2 Spares Issue 5 February 1997 ...
Страница 85: ...Lucent Technologies ECS Minicell Battery Plant H569 420 9 4 Product Warranty Issue 5 February 1997 ...