Lucent Technologies ECS Minicell Battery Plant H569-420
3 - 8 Engineering and Ordering
Issue 5 February 1997
(All sizes are for 1/4” bolt.) Use “taps” for larger wire size
requirements.
10. For systems ground applications larger than those listed
above, order an adapter kit, comcode 846638575. The
adapter kit will accommodate the cable and lug sizes in the
table below. All are sized for a 3/8” bolt.
11. Order the appropriate kit based on lug wire size for use
with the distribution panel.
Table 3-F: Cable and Lug Sizes
Cable
Lug
KS5482 L28FR 6 AWG
WP91412 L-3
KS5482 L28FR 4 AWG
WP91412 L-5
KS5482 L28FR 2 AWG
WP91412 L-54
KS5482 L28FR 1 AWG
WP91412 L-8
KS20921 6 AWG
WP91412 L-3
KS20921 4 AWG
WP91412 L-54
KS20921 2 AWG
WP91412 L-8
Table 3-G: Cable and Lug Sizes
Cable
Lug
KS5482 L28FR 1/0 AWG
WP91412 L-56
KS5482 L28FR 2/0 AWG
WP91412 L-57
KS5482 L28FR 3/0 AWG
WP91412 L-77
KS5482 L28FR 4/0 AWG
WP91412 L-59
KS20921 1/0 AWG
WP91412 L-57
KS20921 2/0 AWG
WP91412 L-77
KS20921 3/0 AWG
WP91412 L-59
KS20921 4/0 AWG
WP91412 L-27
Table 3-H: Terminal Lug Kits for 3 - 50 Ampere Circuit
Breakers
Wire Size
Comcode
Kit Contents
Die
10 -12
AWG
847301660
(1) WP91412 L-73 Double Hole Term
(1) WP91412 L-93 Single Hole Term
(1) 10-32x7/16 Screw
(2) WP91767 L-3 1/4 Tubing 2 in.
R-5473-5
8 AWG
847301678
(1) WP91412 L-52 Double Hole Term
(1) WP91412 L-1 Single Hole Term
(2) 10-32x7/16 Screw
(2) WP91767 L-4 3/8 Tubing 2 in.
Red
Содержание H569-420
Страница 2: ......
Страница 7: ...Lucent Technologies ECS Minicell Battery Plant H569 420 2 List of Figures Issue 5 February 1997 ...
Страница 15: ...Lucent Technologies ECS Minicell Battery Plant H569 420 1 6 Introduction Issue 5 February 1997 ...
Страница 71: ...Lucent Technologies ECS Minicell Battery Plant H569 420 6 8 Installation Tables Issue 5 February 1997 ...
Страница 81: ...Lucent Technologies ECS Minicell Battery Plant H569 420 8 2 Spares Issue 5 February 1997 ...
Страница 85: ...Lucent Technologies ECS Minicell Battery Plant H569 420 9 4 Product Warranty Issue 5 February 1997 ...