Other groups on the H569-420 drawing are ordered as
“Equipped With (E/W)” items. This means that they are ordered
in addition to a main group and will be installed in the factory. If
these groups are ordered as separate items, they will be shipped
to you in separate containers to be assembled during installation.
Some items such as circuit breakers and mounting hardware are
always ordered separately.
The following table provides a summary of the H569-420 group
structure. Please read all of the notes carefully before ordering.
Table 3-A: +24V Minicell Battery Plant (H569-420)
Group
Number
Description
1
46.0” framework assembly arrange for use with 24V,
600AH batteries and stand. See notes 5, 28, and 29.
2
42.0” framework assembly for mounting on a four-shelf
battery stand. See Group 10 and notes 5, 28, 29, and 30.
3
Reserved for future use.
4
Equipment, wiring, and hardware for one +24V 300
ampere rectifier shelf assembly (RSA 1)with 208/240volt
ac input. Order Group 4 in addition to either Group 1 or
Group 2. See notes 5, 20, and 26.
5
Equipment, wiring, and hardware for one +24V 300
ampere rectifier shelf assembly (RSA 2) with 208/240volt
ac input. Order Group 5 in addition to either Group 1 e/w
Group 4 or Group 2 e/w Group 4. See notes 20 and 27.
6
Assembly, wiring, and equipment for one ECS controller.
Always required in addition to either Group 1 or
Group 2.
7
Assembly, wiring, and equipment for one +24V, 600
ampere output distribution panel equipped with low
voltage disconnect/reconnect feature (600 ampere).
NOTE: One Group 7 or one Group 8 always required in
addition to either Group 1 or Group 2.
8
Assembly, wiring, and equipment for one +24V, 600
ampere output distribution panel. NOTE: One Group 7 or
one Group 8 always required in addition to either
Group 1 or Group 2.
9
Reserved for future use.
10
Four-shelf battery stand for two strings of Lucent
2VR375E 24V batteries.See notes 20, 29, and 30.
A
Optional equipment in addition to Group-6 (plant
controller) provides microprocessor circuit pack (CP2).
CP2 provides remote/local monitoring and control
functions. See note 21.
B
Same as Group A (CP2) equipped with voice response
feature. See note 22.
Содержание H569-420
Страница 2: ......
Страница 7: ...Lucent Technologies ECS Minicell Battery Plant H569 420 2 List of Figures Issue 5 February 1997 ...
Страница 15: ...Lucent Technologies ECS Minicell Battery Plant H569 420 1 6 Introduction Issue 5 February 1997 ...
Страница 71: ...Lucent Technologies ECS Minicell Battery Plant H569 420 6 8 Installation Tables Issue 5 February 1997 ...
Страница 81: ...Lucent Technologies ECS Minicell Battery Plant H569 420 8 2 Spares Issue 5 February 1997 ...
Страница 85: ...Lucent Technologies ECS Minicell Battery Plant H569 420 9 4 Product Warranty Issue 5 February 1997 ...