Lucent Technologies ECS Minicell Battery Plant H569-420
Issue 5 February 1997
Installation Tables 6 - 3
Rectifier
Table 6-C: CP2 Dip Switch Settings
SW20
2
Function
Option
Switch Setting
-1
Remote TR
Enabled
0
Disabled
1
-2
-3
-4
-2
Shunt Size
600 amperes
0
0
1
-3
-4
-5
Reserved
-6
Maximum # of
rectifiers
6 Rectifiers
1
-7
Nominal Battery
Plant Voltage
+24 Volts
1
-8
Local Port
Terminal
0
Printer
1
Table 6-D: SW701 Settings for SR100/+24V Rectifier
Internal Selective High Voltage Shutdown
(Volts)
Load Share
Enable Disable
-1
-2-
3-
4-
-5
+25.0V
1
1
1
1
1
0
+25.5V
1
1
1
0
1
0
+26.0V
1
1
0
1
1
0
+26.5V
1
1
0
0
1
0
+27.0V
1
0
1
1
1
0
+27.5V
1
0
1
0
1
0
+28.0V
1
0
0
1
1
0
+28.5V
1
0
0
0
1
0
+29.0V
0
1
1
1
1
0
Содержание H569-420
Страница 2: ......
Страница 7: ...Lucent Technologies ECS Minicell Battery Plant H569 420 2 List of Figures Issue 5 February 1997 ...
Страница 15: ...Lucent Technologies ECS Minicell Battery Plant H569 420 1 6 Introduction Issue 5 February 1997 ...
Страница 71: ...Lucent Technologies ECS Minicell Battery Plant H569 420 6 8 Installation Tables Issue 5 February 1997 ...
Страница 81: ...Lucent Technologies ECS Minicell Battery Plant H569 420 8 2 Spares Issue 5 February 1997 ...
Страница 85: ...Lucent Technologies ECS Minicell Battery Plant H569 420 9 4 Product Warranty Issue 5 February 1997 ...