Engineering and Ordering 3 - 11
stand. The Group 1 plant accommodates up to two rectifier
shelves as well as a converter shelf.
A Group 2 plant can accommodate only one rectifier shelf
(Group 4) if it is equipped with a converter shelf assembly
(Group N).
15. Group G provides a thermal compensation unit which
monitors the temperature of a battery string and provides
an isolated contact closure when the battery exceeds 42°C.
The Battery Thermal Management product manual (select
code 157-010-200, comcode 107224445) provides
additional information.
16. Each distribution module has a maximum of 42 positions.
Circuit breakers rated between 3 and 50 amperes occupy
one position. Breakers rated from 60 to 100 amperes
occupy two positions. Two-position circuit breakers
should only be installed in the top row (positions 12-21
and 32-41).
17. Refer to the table below for ordering information for the
plug-in circuit breakers used in the distribution modules
(Groups 7 and 8). Tables 3-H and 3-I contain ordering
information for termination lugs and hardware which are
not provided with the circuit breakers.
Table 3-L: Circuit Breakers for Groups 7 and 8
Description
Comcode
KS23616 L#
3 ampere circuit breaker
407098417
31
5 ampere circuit breaker
407098425
32
10 ampere circuit breaker
407098433
33
15 ampere circuit breaker
407098458
34
20 ampere circuit breaker
407098474
36
25 ampere circuit breaker
407098482
37
30 ampere circuit breaker
407098490
38
40 ampere circuit breaker
407245448
48
45 ampere circuit breaker
407098516
40
50 ampere circuit breaker
407098524
41
60 ampere circuit breaker*
407098532
42
70 ampere circuit breaker*
407098540
43
80 ampere circuit breaker*
407098557
44
90 ampere circuit breaker*
407098565
45
100 ampere circuit breaker*
407098573
46
Содержание H569-420
Страница 2: ......
Страница 7: ...Lucent Technologies ECS Minicell Battery Plant H569 420 2 List of Figures Issue 5 February 1997 ...
Страница 15: ...Lucent Technologies ECS Minicell Battery Plant H569 420 1 6 Introduction Issue 5 February 1997 ...
Страница 71: ...Lucent Technologies ECS Minicell Battery Plant H569 420 6 8 Installation Tables Issue 5 February 1997 ...
Страница 81: ...Lucent Technologies ECS Minicell Battery Plant H569 420 8 2 Spares Issue 5 February 1997 ...
Страница 85: ...Lucent Technologies ECS Minicell Battery Plant H569 420 9 4 Product Warranty Issue 5 February 1997 ...