16 Appendix A – Factory Default Setups
45
16 Appendix A – Factory Default Setups
Parameters pH
Redox
Units pH
mV
Electrode Type
Glass
N/A
Temperature Units
°
C
°
C
Temperature Compensation
Automatic
N/A
Fixed Temperature Input
+25.0
°
C +25.0
°
C
Set Points
SP1 Source
Sensor
Sensor
SP1 Trigger
Low
Low
SP1 Level ( Band High )
7.00pH
200mV
SP1 Band Low
4.00pH
100mV
SP1 Mode
On/Off
On/Off
SP1 Dose Alarm
No
No
SP1 Alarm Time (mm:ss)
05:00
05:00
SP1 Delay ( mm:ss )
00:00
00:00
SP1 Hysteresis ( % of SP Level )
1.0%
1.0%
SP1 Cycle Time ( mm:ss )
00:30
00:30
SP1 Proportional Band
( % of range )
20.0% 20.0%
SP2 Source
Sensor
Sensor
SP2 Trigger
High
High
SP2 Level ( Band High )
9.00pH
300mV
SP2 Band Low
4.00pH
100.0mV
SP2 Mode
On/Off
On/Off
SP2 Dose Alarm
No
No
SP2 Alarm Time (mm:ss)
05:00
05:00
SP2 Delay ( mm:ss )
00:00
00:00
SP2 Hysteresis ( % of SP Level )
1.0%
1.0%
SP2 Cycle Time ( mm:ss )
00:30
00:30
SP2 Proportional Band (% of
range)
20.0% 20.0%