3. Wiring Method
3-18
3.4.2
Timing Diagram at the Time of Alarm Trigger
When the alarm triggered in the servo drive, it blocks the PWM and the motor stops.
Caution
After solving the problem that triggered the alarm, and changing the command signal (Servo
ON) to OFF, reset the alarm.
200 ms
Control power
establishment
5 [V]
Control
program
Reset
Main power
establishment
Alarm
(Normally On)
Servo RDY
Servo On
Clear DB
PWM
(Motor rotation)
RESET
150 ms
40 ms
10 ms
5 ms
2 ms
30 ms
Alarm triggered by
an anomaly
Remove
causes that
triggered
alarm
Main power,
control power
supply