4. Parameters
4-54
4.
System ID setting
An ID can be given to the servo if RS422 communication and BUS communication are used for
communication with the servo. Communication-related options are required in this case.
Communication speed setting [P0-04]
You can select the baud rate, the communication speed of RS422.
0: 9600 [bps]
1: 19200 [bps]
2: 38400 [bps]
3: 57600 [bps]
System ID [P0-05]
A unique ID can be given to the servo and used for individual communication with it.
5.
Main power input mode setting [P0-06]
Sets the main power input mode and processing mode in case of phase loss.
DIGIT 1: Sets the main power input type.
(0: Single-phase power input. 1: Three-phase power input.)
DIGIT 2: Sets how to handle errors and warnings in case of main power phase loss.
(0: Error in case of main power phase loss. 1: Warning in case of main power phase loss.)
6.
RST checking time setting [P0-07]
Sets checking time for main power phase loss.
7.
Start-up display parameter setting [P0-08]
You can set the parameter to be applied when the servo is turned on.
There are 26 values available for setting, from [St-00] to [St-25]. Choose one for a specific
parameter.
8.
Regenerative overload derating factor setting [P0-09]
Sets derating factor for checking of regenerative resistance overload. When the derating value is
set to 100% or below, the overload alarm triggers at a time proportional to the set value.
9.
Regenerative resistance value setting [P0-10]
Sets the resistance value for regenerative braking resistance. If set to 0, a default resistance
capacity embedded in the drive is used.
10.
Regenerative resistance capacity setting [P0-11]
Sets the capacity for the current regenerative resistance. If set to 0, a default resistance capacity
embedded in the drive is used.
11.
Overload check default load factor setting [P0-12]
Indicates the load factor for starting continuous overload checks. If set to 100 or below, an overload
check starts early and the overload alarm triggers early.
12.
Overload warning level setting [P0-13]
Sets the level for continuous overload warning signal output. A warning signal is issued when the
percentage value set relative to the alarm trigger value is reached.
13.
Encoder pulse prescale output (encoder output scaling[P0-14])
Содержание XDL-L7SA001X
Страница 2: ......
Страница 38: ...2 Installation 2 6 ...
Страница 48: ...3 Wiring Method 3 10 3 3 Example of connecting to PLC 3 3 1 XGT PLC 1 XGF PO1 2 3A Open Collector ...
Страница 63: ...3 Wiring Method 3 25 3 7 Serial Encoder Signaling Unit CN2 Wiring 3 7 1 XLCS E CS Cable 3 7 2 XLCS E DS Cable ...
Страница 68: ......
Страница 142: ......
Страница 166: ......
Страница 232: ...7 Product Specifications 7 48 FCL Series XML FCL04A FCL03D FCL06A FCL05D FCL08A FCL06D FCL10A FCL07D ...