5. Handling and Operation
5-14
(2)
Example of Output Contact Forced ON/OFF
(BRAKE OFF)
[Example of handling output contact forced ON/OFF]
Order
Loader Displays
Keys to Use
What to Do
1
Press [MODE] to move to [Cn-00].
2
Press [UP] or [DOWN] to move to
[Cn-08].
3
Press [SET] to enter input forced
ON/OFF setting.
4
Press [SET] to enter forced output bit
setting.
5
Press [MODE] at the blinking cursor
to move to the desired digit, DIGIT 2,
and it rotates.
6
Press [UP] to turn off the brake
signal.
7
Press [SET] to end input forced
ON/OFF mode.
[done] is displayed.
8
Press [MODE] for a second to return
to [Cn-08].
※
“ ” indicates flickering.